| Assessment Year | 2015 |
|---|---|
| Principal Product | Processed meat |
| NAICS | 311612: Meat Processed from Carcasses |
| SIC | 2013: Sausages and Other Prepared Meat Products |
| Sales Range | $10 M to 50M |
| # of Employees | 469 |
| Plant Area |
189,000
ft2
|
| Annual Production | 140,000,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Kansas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,410,007 | 25,855,500 |
kWh
|
$0.055 |
| Electricity Demand | $580,883 | 46,805 |
kW-mo/yr
|
$12.41 |
| Natural Gas | $940,001 | 175,545 |
MMBtu
|
$5.35 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $408,102 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $82,568 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7261: Install timers and/or thermostats | $3,077 | - |
$1,828
33,230
kWh
|
- | - |
$1,249
-
MMBtu
|
|
| 02 | 2.7241: Install outside air damper / economizer on hvac unit | $2,799 | $7,680 |
$2,799
50,894
kWh
|
- | - | - | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $4,249 | $8,691 |
$4,249
77,259
kWh
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $797 | $3,904 |
$797
14,498
kWh
|
- | - | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,514 | $34,454 |
$8,461
153,834
kWh
|
$3,053
-
kW-mo/yr
|
- | - | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $10,211 | $2,000 | - | - | - |
$10,211
-
MMBtu
|
|
| 07 | 2.2136: Install / repair insulation on steam lines | $300 | $377 | - | - | - |
$300
-
MMBtu
|
|
| 08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $34,856 | $41,000 | - | - | - |
$34,856
-
MMBtu
|
|
| 09 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $1,404 | $824 | - | - | - |
$1,404
-
MMBtu
|
|
| 10 | 2.4221: Install compressor air intakes in coolest locations | $4,060 | $1,875 |
$4,060
73,822
kWh
|
- | - | - | |
| 11 | 2.2437: Recover waste heat from equipment | $25,364 | $2,846 |
$11,669
212,160
kWh
|
- | - |
$13,695
-
MMBtu
|
|
| 12 | 2.2437: Recover waste heat from equipment | $43,900 | $87,882 |
$(-1,076.3)
(-19,569)
kWh
|
$(-333.2)
-
kW-mo/yr
|
- |
$45,309
-
MMBtu
|
|
| 13 | 2.3417: Use waste heat with a closed-cycle gas turbine-generator set to cogenerate electricity and heat | $265,571 | $1,832,665 | - | - | $173,047 |
$92,524
-
MMBtu
|
|
| TOTAL RECOMMENDED | $408,102 | $2,024,198 |
$32,787
596,128
kWh
|
$2,720
-
kW-mo/yr
|
$173,047 |
$199,548
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $82,568 | $60,129 |
$21,153
384,604
kWh
|
- | - |
$61,415
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs