Assessment Year | 2018 |
---|---|
Principal Product | Electronics Chemical Manufacturing |
NAICS | 334413: Semiconductor and Related Device Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $100 M to 500M |
# of Employees | 200 |
Plant Area |
100,000
ft2
|
Annual Production | 100
Tgal
|
Production Hrs. Annual | 4,400
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $772,825 | 8,209,597 |
kWh
|
$0.094 |
Electricity Demand | $407,779 | 14,196 |
kW-mo/yr
|
$28.72 |
Natural Gas | $268,265 | 29,195 |
MMBtu
|
$9.19 |
TOTAL YEARLY COSTS | $1,448,869 | |||
RECOMMENDED SAVINGS* | $29,910 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,330 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,402 | $11,547 |
$7,335
77,921
kWh
|
$3,067
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,330 | $22,874 |
$6,666
70,808
kWh
|
$4,218
-
kW-mo/yr
|
- | $467 | $(-21.0) | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $8,178 | $27,403 |
$8,164
86,724
kWh
|
$3,413
-
kW-mo/yr
|
$(-3,399.0)
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $29,910 | $61,824 |
$22,165
235,453
kWh
|
$10,698
-
kW-mo/yr
|
$(-3,399.0)
-
MMBtu
|
$467 | $(-21.0) | ||
TOTAL IMPLEMENTED | $11,330 | $22,874 |
$6,666
70,808
kWh
|
$4,218
-
kW-mo/yr
|
- | $467 | $(-21.0) |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs