Assessment Year 2014
Principal Product Aviation fuel filters
NAICS 333999: All Other Miscellaneous General Purpose Machinery Manufacturing
SIC 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 150
Plant Area 72,000
ft2
Annual Production 700,000
pieces
Production Hrs. Annual 4,810
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $193,406 2,406,160
kWh
Electricity Demand $18,673 8,566
kW-mo/yr
Natural Gas $181,984 25,221
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $45,605 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $10,101

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.4221: Install compressor air intakes in coolest locations $1,242 $1,588 $1,242
15,527
kWh
-
02 2.2437: Recover waste heat from equipment $6,653 $1,751 - $6,653
-
MMBtu
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,702 $400 $2,702
33,772
kWh
-
04 2.7142: Utilize higher efficiency lamps and/or ballasts $3,435 $16,592 $3,435
42,935
kWh
-
05 2.7232: Replace existing hvac unit with high efficiency model $9,020 $43,252 $9,020
112,752
kWh
-
06 2.7241: Install outside air damper / economizer on hvac unit $13,523 $7,700 $13,523
169,042
kWh
-
07 2.7261: Install timers and/or thermostats $746 $169 $645
8,059
kWh
$101
-
MMBtu
08 2.2414: Use waste heat from hot flue gases to preheat $6,458 $28,800 - $6,458
-
MMBtu
09 2.2414: Use waste heat from hot flue gases to preheat $1,826 $9,200 - $1,826
-
MMBtu
TOTAL RECOMMENDED $45,605 $109,452 $30,567
382,087
kWh
$15,038
-
MMBtu
TOTAL IMPLEMENTED $10,101 $2,320 $3,347
41,831
kWh
$6,754
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs