Assessment Year | 2014 |
---|---|
Principal Product | Fans, Blowers and Ventilation Equipments |
NAICS | 333413: Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing |
SIC | 3564: Industrial and Commercial Fans and Blowers and Air Purification Equipment |
Sales Range | $10 M to 50M |
# of Employees | 264 |
Plant Area |
350,000
ft2
|
Annual Production | 20,000
pieces
|
Production Hrs. Annual | 4,524
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $179,884 | 3,650,400 |
kWh
|
$0.049 |
Electricity Demand | $61,596 | 10,620 |
kW-mo/yr
|
$5.80 |
Natural Gas | $90,657 | 18,571 |
MMBtu
|
$4.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $80,018 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $46,137 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,554 | $1,400 |
$8,554
174,564
kWh
|
- | - | - | |
02 | 2.4322: Use or replace with energy efficient substitutes | $3,459 | $5,148 |
$3,459
70,599
kWh
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,296 | $1,222 |
$1,296
26,449
kWh
|
- | - | - | |
04 | 2.6231: Utilize controls to operate equipment only when needed | $3,905 | $262 |
$3,905
79,697
kWh
|
- | - | - | |
05 | 2.6127: Maintain air filters by cleaning or replacement | $229 | $525 |
$229
4,671
kWh
|
- | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,064 | $3,192 |
$1,064
21,709
kWh
|
- | - | - | |
07 | 2.7211: Clean and maintain refrigerant condensers and towers | $3,821 | $2,573 |
$2,638
53,836
kWh
|
$1,183
-
kW-mo/yr
|
- | - | |
08 | 2.7241: Install outside air damper / economizer on hvac unit | $18,835 | $13,760 |
$18,835
384,384
kWh
|
- | - | - | |
09 | 2.3212: Optimize plant power factor | $6,235 | $11,638 | - | - | $6,235 | - | |
10 | 2.4322: Use or replace with energy efficient substitutes | $11,228 | $37,188 |
$8,545
174,380
kWh
|
$2,683
-
kW-mo/yr
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,371 | $13,908 |
$2,515
51,317
kWh
|
$856
-
kW-mo/yr
|
- | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,570 | $55,638 |
$8,967
183,006
kWh
|
$2,603
-
kW-mo/yr
|
- | - | |
13 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $217 | $1,073 |
$217
4,428
kWh
|
- | - | - | |
14 | 2.6232: Install set-back timers | $6,234 | $1,983 | - | - | - |
$6,234
-
MMBtu
|
|
TOTAL RECOMMENDED | $80,018 | $149,510 |
$60,223
1,229,040
kWh
|
$7,325
-
kW-mo/yr
|
$6,235 |
$6,234
-
MMBtu
|
||
TOTAL IMPLEMENTED | $46,137 | $116,642 |
$38,811
792,070
kWh
|
$7,325
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs