ITAC Assessment: OK0869
ITAC logo
ITAC Assessment: OK0869
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2013
Principal Product Healthcare
NAICS 622110: General Medical and Surgical Hospitals
SIC 8062: General Medical and Surgical Hospitals
Sales Range $10
M
to 50
M
# of Employees 700
Plant Area 265,000
ft2
Annual Production 0
units
Production Hrs. Annual 8,760
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $503,661 9,382,800
kWh
Electricity Demand $69,948 15,544
kW-mo/yr
Natural Gas $213,921 54,055
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $142,040 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $62,062

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.1233: Analyze flue gas for proper air/fuel ratio $9,817 $16,000 - - $9,817
-
MMBtu
02 2.7232: Replace existing hvac unit with high efficiency model $6,981 $12,378 - - $6,981
-
MMBtu
03 2.2113: Repair or replace steam traps $999 $1,850 - - $999
-
MMBtu
04 2.1232: Keep boiler tubes clean $9,106 $3,420 - - $9,106
-
MMBtu
05 2.7135: Install occupancy sensors $13,630 $23,667 $13,630
252,403
kWh
- -
06 2.7211: Clean and maintain refrigerant condensers and towers $4,056 $2,140 $3,487
64,570
kWh
$569
-
kW-mo/yr
-
07 2.7241: Install outside air damper / economizer on hvac unit $11,267 $20,900 $11,267
208,656
kWh
- -
08 2.6232: Install set-back timers $2,563 - $971
17,979
kWh
- $1,592
-
MMBtu
09 2.2691: Shut off cooling if cold outside air will cool process $38,010 $23,834 $38,010
703,890
kWh
- -
10 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $9,424 $21,368 $9,424
174,522
kWh
- -
11 2.2625: Chill water to the highest temperature possible $22,243 - $22,243
369,707
kWh
- -
12 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $2,035 $5,256 $2,035
37,681
kWh
- -
13 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $10,890 $21,025 $10,890
201,669
kWh
- -
14 2.4221: Install compressor air intakes in coolest locations $1,019 $2,132 $1,019
18,871
kWh
- -
TOTAL RECOMMENDED $142,040 $153,970 $112,977
2,049,948
kWh
$569
-
kW-mo/yr
$28,495
-
MMBtu
TOTAL IMPLEMENTED $62,062 $50,419 $52,387
970,129
kWh
$569
-
kW-mo/yr
$9,106
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs