Assessment Year 2013
Principal Product Pizza crust & pastries
NAICS 311813: Frozen Cakes, Pies, and Other Pastries Manufacturing
SIC 2038: Frozen Specialties, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 65
Plant Area 80,000
ft2
Annual Production 15,000,000
lb
Production Hrs. Annual 4,160
hrs
Location (State) Oklahoma

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $160,875 2,827,596
kWh
Electricity Demand $49,318 8,225
kW-mo/yr
Natural Gas $36,363 6,780
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $71,914 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,534

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7241: Install outside air damper / economizer on hvac unit $18,260 $28,000 $18,260
320,355
kWh
- -
02 2.7232: Replace existing hvac unit with high efficiency model $14,259 $28,400 $11,793
206,902
kWh
$2,466
-
kW-mo/yr
-
03 2.2628: Utilize a less expensive cooling method $19,312 $184,080 $16,013
280,938
kWh
$3,299
-
kW-mo/yr
-
04 2.7211: Clean and maintain refrigerant condensers and towers $4,776 $1,440 $3,960
69,458
kWh
$816
-
kW-mo/yr
-
05 2.6232: Install set-back timers $449 $318 $165
2,899
kWh
- $284
-
MMBtu
06 2.7142: Utilize higher efficiency lamps and/or ballasts $865 $3,992 $865
15,170
kWh
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $2,853 $22,216 $2,205
38,687
kWh
$648
-
kW-mo/yr
-
08 2.4221: Install compressor air intakes in coolest locations $299 $463 $299
5,242
kWh
- -
09 2.2437: Recover waste heat from equipment $5,915 $2,598 - - $5,915
-
MMBtu
10 2.2121: Increase amount of condensate returned $1,019 $700 - - $1,019
-
MMBtu
11 2.2511: Insulate bare equipment $232 $280 - - $232
-
MMBtu
12 2.1231: Establish burner maintenance schedule for boilers $2,408 $2,686 $2,408
42,257
kWh
- -
13 2.7491: Insulate glazing, walls, ceilings, and roofs $189 $2,098 $115
2,009
kWh
- $75
-
MMBtu
14 2.7423: Reduce heat gain by window tinting $1,077 $16,000 $573
10,052
kWh
- $504
-
MMBtu
TOTAL RECOMMENDED $71,914 $293,271 $56,656
993,968
kWh
$7,229
-
kW-mo/yr
$8,029
-
MMBtu
TOTAL IMPLEMENTED $6,534 $18,038 $4,698
82,409
kWh
$816
-
kW-mo/yr
$1,020
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings