Assessment Year | 2013 |
---|---|
Principal Product | Electric Motors |
NAICS | 335312: Motor and Generator Manufacturing |
SIC | 3621: Motors and Generators |
Sales Range | $100 M to 500M |
# of Employees | 438 |
Plant Area |
220,000
ft2
|
Annual Production | 150,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $613,771 | 7,924,975 |
kWh
|
$0.077 |
Electricity Demand | $56,830 | 26,069 |
kW-mo/yr
|
$2.18 |
Natural Gas | $58,986 | 8,572 |
MMBtu
|
$6.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $98,294 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $67,331 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6232: Install set-back timers | $2,575 | $1,530 |
$992
12,888
kWh
|
- | - |
$1,582
-
MMBtu
|
|
02 | 2.7241: Install outside air damper / economizer on hvac unit | $47,613 | $33,780 |
$47,613
618,348
kWh
|
- | - | - | |
03 | 2.7211: Clean and maintain refrigerant condensers and towers | $5,494 | $1,776 |
$5,097
66,197
kWh
|
$397
-
kW-mo/yr
|
- | - | |
04 | 2.7243: Improve air circulation with destratification fans / other methods | $12,200 | $9,900 |
$6,008
78,019
kWh
|
- | - |
$6,192
-
MMBtu
|
|
05 | 2.7135: Install occupancy sensors | $138 | $1,771 |
$138
1,788
kWh
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,091 | $35,380 |
$4,091
53,136
kWh
|
- | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,472 | $1,050 |
$9,472
123,011
kWh
|
- | - | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $2,177 | $462 |
$2,177
28,278
kWh
|
- | - | - | |
09 | 2.2437: Recover waste heat from equipment | $7,362 | $1,220 | - | - | - |
$7,362
-
MMBtu
|
|
10 | 2.4322: Use or replace with energy efficient substitutes | $3,044 | $3,080 |
$3,044
39,527
kWh
|
- | - | - | |
11 | 2.3212: Optimize plant power factor | $4,129 | $11,222 | - | - | $4,129 | - | |
TOTAL RECOMMENDED | $98,294 | $101,171 |
$78,632
1,021,192
kWh
|
$397
-
kW-mo/yr
|
$4,129 |
$15,136
-
MMBtu
|
||
TOTAL IMPLEMENTED | $67,331 | $38,598 |
$65,352
848,722
kWh
|
$397
-
kW-mo/yr
|
- |
$1,582
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs