Assessment Year | 2009 |
---|---|
Principal Product | Plastic Stretch Films |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
130,000
ft2
|
Annual Production | 82,495,387
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,456,581 | 21,470,400 |
kWh
|
$0.068 |
Natural Gas | $12,368 | 989 |
MMBtu
|
$12.51 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $228,978 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $224,089 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2612: Use cooling tower water instead of refrigeration | $164,328 | $490,000 |
$164,328
2,434,500
kWh
|
- | |
02 | 2.2625: Chill water to the highest temperature possible | $26,234 | - |
$26,234
391,564
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,889 | $19,448 |
$4,889
72,965
kWh
|
- | |
04 | 2.4221: Install compressor air intakes in coolest locations | $2,136 | $3,129 |
$2,136
31,886
kWh
|
- | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $28,753 | $33,300 |
$28,753
425,979
kWh
|
- | |
06 | 2.7261: Install timers and/or thermostats | $2,638 | $779 | - |
$2,638
-
MMBtu
|
|
TOTAL RECOMMENDED | $228,978 | $546,656 |
$226,340
3,356,894
kWh
|
$2,638
-
MMBtu
|
||
TOTAL IMPLEMENTED | $224,089 | $527,208 |
$221,451
3,283,929
kWh
|
$2,638
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs