Assessment Year | 1997 |
---|---|
Principal Product | Wallboard Paper |
NAICS |
n/a
|
SIC | 2631: Paperboard Mills |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
250,000
ft2
|
Annual Production | 104,400
ton
|
Production Hrs. Annual | 8,520
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $765,758 | 42,732,123 |
kWh
|
$0.018 |
Electricity Fees | $528,797 | - |
|
- |
Natural Gas | $1,665,257 | 1,697,939 |
MMBtu
|
$0.98 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $820,674 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $76,528 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,003 | $1,048 |
$589
30,774
kWh
|
$414
-
kW-mo/yr
|
- | - | - | |
02 | 2.2136: Install / repair insulation on steam lines | $1,233 | $343 | - | - |
$1,233
-
MMBtu
|
- | - | |
03 | 2.2135: Repair and eliminate steam leaks | $27,432 | $3,300 | - | - |
$27,432
-
MMBtu
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,204 | $5,551 |
$559
31,067
kWh
|
$645
-
kW-mo/yr
|
- | - | - | |
05 | 2.6232: Install set-back timers | $331 | $126 | - | - |
$331
-
MMBtu
|
- | - | |
06 | 2.6218: Turn off equipment when not in use | $3,859 | - |
$1,099
61,254
kWh
|
$2,760
-
kW-mo/yr
|
- | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,226 | $9,259 |
$5,262
293,669
kWh
|
$3,964
-
kW-mo/yr
|
- | - | - | |
08 | 3.5131: Recycle white water | $729,526 | $4,000,000 | - | - | - |
$729,526
-
Tgal
|
- | |
09 | 4.423: Move product using mechanical means | $46,860 | $72,000 | - | - | - | - | $46,860 | |
TOTAL RECOMMENDED | $820,674 | $4,091,627 |
$7,509
416,764
kWh
|
$7,783
-
kW-mo/yr
|
$28,996
-
MMBtu
|
$729,526
-
Tgal
|
$46,860 | ||
TOTAL IMPLEMENTED | $76,528 | $76,691 |
$589
30,774
kWh
|
$414
-
kW-mo/yr
|
$28,665
-
MMBtu
|
- | $46,860 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs