Assessment Year | 1983 |
---|---|
Principal Product | POLYETHYLENE PIPE |
NAICS |
n/a
|
SIC | 3084: Plastics Pipe |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
n/a
|
Annual Production | 27,600,000
lb
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $268,521 | 9,028,136 |
kWh
|
$0.030 |
Natural Gas | $12,147 | 3,948 |
MMBtu
|
$3.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $11,043 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $115 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3191: Use demand controller or load shedder | $4,150 | $913 |
$4,150
-
kWh
|
- | |
02 | 2.4221: Install compressor air intakes in coolest locations | $115 | $187 |
$115
5,569
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $248 | $203 |
$248
4,689
kWh
|
- | |
04 | 2.7261: Install timers and/or thermostats | $178 | $377 | - |
$178
-
MMBtu
|
|
05 | 2.6212: Turn off equipment during breaks, reduce operating time | $800 | $180 |
$800
38,687
kWh
|
- | |
06 | 2.2515: Use optimum thickness insulation | $1,025 | $832 |
$1,025
49,824
kWh
|
- | |
07 | 2.2694: Use highest temperature for chilling or cold storage | $4,195 | $300 |
$4,195
203,400
kWh
|
- | |
08 | 2.6242: Minimize operation of equipment maintained in standby condition | $332 | $45 |
$332
16,120
kWh
|
- | |
TOTAL RECOMMENDED | $11,043 | $3,037 |
$10,865
318,289
kWh
|
$178
-
MMBtu
|
||
TOTAL IMPLEMENTED | $115 | $187 |
$115
5,569
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs