Assessment Year | 1997 |
---|---|
Principal Product | Plastic Trays |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 50 |
Plant Area |
40,000
ft2
|
Annual Production | 4,000,000
lb
|
Production Hrs. Annual | 6,365
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $110,379 | 2,471,571 |
kWh
|
$0.045 |
Electricity Demand | $51,934 | 8,775 |
kW-mo/yr
|
$5.92 |
Electricity Fees | $1,244 | - |
|
- |
Natural Gas | $12,423 | 2,730 |
MMBtu
|
$4.55 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,851 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $10,737 | $650 | n/a |
$8,592
192,263
kWh
|
$2,145
-
kW-mo/yr
|
- | - | - | - |
02 | 2.7135: Install occupancy sensors | $752 | $246 | n/a |
$639
14,361
kWh
|
$113
-
kW-mo/yr
|
- | - | - | - |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,686 | $946 | n/a |
$3,735
83,529
kWh
|
$951
-
kW-mo/yr
|
- | - | - | - |
04 | 2.3414: Burn waste to produce steam to drive a steam turbine generator set and use steam exhaust for heat | $8,425 | $815 | n/a | - | - | - |
$8,425
-
MMBtu
|
- | - |
05 | 2.4221: Install compressor air intakes in coolest locations | $483 | $250 | n/a |
$483
10,844
kWh
|
- | - | - | - | - |
06 | 2.4133: Use most efficient type of electric motors | $967 | $824 | n/a |
$774
17,292
kWh
|
$193
-
kW-mo/yr
|
- | - | - | - |
07 | 2.7261: Install timers and/or thermostats | $240 | $180 | n/a |
$64
1,465
kWh
|
- | - |
$176
-
MMBtu
|
- | - |
08 | 2.3212: Optimize plant power factor | $356 | $1,047 | n/a | - | - | $356 | - | - | - |
09 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $3,890 | $840 | n/a |
$3,110
69,461
kWh
|
$780
-
kW-mo/yr
|
- | - | - | - |
10 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $3,804 | - | n/a | - | - | - | - | - | $3,804 |
11 | 3.4116: Meter recycled water (to reduce sewer charges) | $300 | $120 | n/a | - | - | - | - |
$300
-
Tgal
|
- |
12 | 2.3132: Recharge batteries on during off-peak demand periods | $211 | $50 | n/a | - | - | - | - | - | $211 |
TOTAL RECOMMENDED | $34,851 | $5,968 |
$17,397
389,215
kWh
|
$4,182
-
kW-mo/yr
|
$356 |
$8,601
-
MMBtu
|
$300
-
Tgal
|
$4,015 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||