Assessment Year | 1995 |
---|---|
Principal Product | Hot Rolled Steel Bars |
NAICS |
n/a
|
SIC | 3556: Food Products Machinery |
Sales Range | $10 M to 50M |
# of Employees | 85 |
Plant Area |
43,200
ft2
|
Annual Production | 2,500,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Nevada |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $272,145 | 3,322,099 |
kWh
|
$0.082 |
Natural Gas | $135,278 | 29,886 |
MMBtu
|
$4.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $57,798 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,715 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $17,180 | - |
$17,180
210,141
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,777 | $22,381 |
$13,777
168,816
kWh
|
- | |
03 | 2.7444: Close holes and openings in building such as broken windows | $5,257 | $5,037 | - |
$5,257
-
MMBtu
|
|
04 | 2.4133: Use most efficient type of electric motors | $1,572 | $687 |
$1,572
19,343
kWh
|
- | |
05 | 2.6218: Turn off equipment when not in use | $2,315 | $649 |
$2,315
28,429
kWh
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,811 | $500 |
$4,811
58,910
kWh
|
- | |
07 | 2.3212: Optimize plant power factor | $2,991 | $8,190 |
$2,991
-
kWh
|
- | |
08 | 2.7224: Reduce space conditioning during non-working hours | $1,330 | $27 | - |
$1,330
-
MMBtu
|
|
09 | 2.6218: Turn off equipment when not in use | $7,818 | - |
$7,818
95,545
kWh
|
- | |
10 | 2.4222: Install adequate dryers on air lines to eliminate blowdown | $747 | - |
$747
9,086
kWh
|
- | |
TOTAL RECOMMENDED | $57,798 | $37,471 |
$51,211
590,270
kWh
|
$6,587
-
MMBtu
|
||
TOTAL IMPLEMENTED | $38,715 | $6,251 |
$32,128
393,025
kWh
|
$6,587
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs