Assessment Year | 2000 |
---|---|
Principal Product | metal stampings |
NAICS |
n/a
|
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 370 |
Plant Area |
148,000
ft2
|
Annual Production | 36,500,000
pieces
|
Production Hrs. Annual | 7,878
hrs
|
Location (State) | Indiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $167,090 | 7,369,285 |
kWh
|
$0.023 |
Electricity Demand | $142,432 | 14,170 |
kW-mo/yr
|
$10.05 |
Natural Gas | $92,106 | 23,982 |
MMBtu
|
$3.84 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,378 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,892 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4151: Develop a repair/replace policy | $8,340 | $22,377 |
$4,981
230,070
kWh
|
$3,359
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $3,206 | - |
$1,808
79,719
kWh
|
$1,220
-
kW-mo/yr
|
- | - | $178 | - | |
03 | 2.7135: Install occupancy sensors | $839 | $600 |
$494
21,688
kWh
|
$345
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $271 | $575 |
$52
2,052
kWh
|
$31
-
kW-mo/yr
|
- | $123 | $65 | - | |
05 | 2.4221: Install compressor air intakes in coolest locations | $3,221 | $1,000 |
$1,924
84,701
kWh
|
$1,297
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $75 | $200 |
$75
3,224
kWh
|
- | - | - | - | - | |
07 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $605 | $400 |
$198
8,792
kWh
|
$543
-
kW-mo/yr
|
$(-136.0)
-
MMBtu
|
- | - | - | |
08 | 3.4151: Minimize water usage | $821 | $2,875 | - | - | - | $250 | $(-227.0) |
$798
-
Tgal
|
|
TOTAL RECOMMENDED | $17,378 | $28,027 |
$9,532
430,246
kWh
|
$6,795
-
kW-mo/yr
|
$(-136.0)
-
MMBtu
|
$373 | $16 |
$798
-
Tgal
|
||
TOTAL IMPLEMENTED | $11,892 | $23,152 |
$6,916
315,065
kWh
|
$4,610
-
kW-mo/yr
|
- | $123 | $243 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs