Assessment Year 1996
Principal Product meat and bread slicers
NAICS
n/a
SIC 3698:
Sales Range $10
M
to 50
M
# of Employees 94
Plant Area 100,000
ft2
Annual Production 7,000
pieces
Production Hrs. Annual 2,210
hrs
Location (State) Indiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $49,587 867,526
kWh
Electricity Demand $28,033 3,411
kW-mo/yr
Electricity Fees $(-1,910.0) -
Natural Gas $50,680 12,528
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $25,651 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $4,851

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings
01 2.7447: Install vinyl strip / high speed / air curtain doors $431 $488 - - $431
-
MMBtu
-
02 2.7494: Install storm windows and doors $9,732 $23,800 $5,293
92,614
kWh
- $4,439
-
MMBtu
-
03 2.2136: Install / repair insulation on steam lines $3,310 $775 - - $3,310
-
MMBtu
-
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $91 $90 $91
1,465
kWh
- - -
05 2.1213: Direct warmest air to combustion intake $178 $800 - - $178
-
MMBtu
-
06 2.4221: Install compressor air intakes in coolest locations $387 $900 $387
5,862
kWh
- - -
07 2.7124: Make a practice of turning off lights when not needed $4,513 - $2,883
50,410
kWh
$1,630
-
kW-mo/yr
- -
08 2.4133: Use most efficient type of electric motors $1,019 $970 $651
11,430
kWh
$368
-
kW-mo/yr
- -
09 2.2123: Insulate feedwater tank $609 $528 - - $609
-
MMBtu
-
10 2.7491: Insulate glazing, walls, ceilings, and roofs $152 $72 - - $152
-
MMBtu
-
11 3.4115: Recover and reuse cooling water $1,718 $6,000 $45
879
kWh
$25
-
kW-mo/yr
- $1,648
-
Tgal
12 3.4157: Replace water cooling on processes with air cooling $3,511 $5,900 $1,190
20,809
kWh
$673
-
kW-mo/yr
- $1,648
-
Tgal
TOTAL RECOMMENDED $25,651 $40,323 $10,540
183,469
kWh
$2,696
-
kW-mo/yr
$9,119
-
MMBtu
$3,296
-
Tgal
TOTAL IMPLEMENTED $4,851 $2,323 $742
12,895
kWh
$368
-
kW-mo/yr
$3,741
-
MMBtu
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs