| Assessment Year | 1995 |
|---|---|
| Principal Product | paints, resins, varnishes |
| NAICS |
n/a
|
| SIC | 2851: Paints, Varnishes, Lacquers, Enamels, and Allied Products |
| Sales Range | $10 M to 50M |
| # of Employees | 90 |
| Plant Area |
83,000
ft2
|
| Annual Production | 1,200
Tgal
|
| Production Hrs. Annual | 8,740
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $87,649 | 1,508,793 |
kWh
|
$0.058 |
| Natural Gas | $71,369 | 15,760 |
MMBtu
|
$4.53 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $28,453 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,107 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4221: Install compressor air intakes in coolest locations | $645 | $200 |
$645
11,430
kWh
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,862 | $295 |
$1,862
33,118
kWh
|
- | |
| 03 | 2.1213: Direct warmest air to combustion intake | $1,653 | $1,500 | - |
$1,653
-
MMBtu
|
|
| 04 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $70 | $92 | - |
$70
-
MMBtu
|
|
| 05 | 2.4133: Use most efficient type of electric motors | $13,304 | $11,130 |
$13,304
296,893
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $786 | $828 |
$786
11,137
kWh
|
- | |
| 07 | 2.8112: Combine utility meters | $3,325 | $3,325 |
$3,325
-
kWh
|
- | |
| 08 | 2.3212: Optimize plant power factor | $5,298 | $3,780 |
$5,298
-
kWh
|
- | |
| 09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $276 | $335 | - |
$276
-
MMBtu
|
|
| 10 | 2.6218: Turn off equipment when not in use | $614 | - |
$614
7,620
kWh
|
- | |
| 11 | 2.2437: Recover waste heat from equipment | $620 | $500 | - |
$620
-
MMBtu
|
|
| TOTAL RECOMMENDED | $28,453 | $21,985 |
$25,834
360,198
kWh
|
$2,619
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $18,107 | $13,288 |
$17,211
360,198
kWh
|
$896
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs