| Assessment Year | 2014 |
|---|---|
| Principal Product | Socks |
| NAICS | 315110: Hosiery and Sock Mills |
| SIC | 2252: Hosiery, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
450,000
ft2
|
| Annual Production | 40,800,000
pieces
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $540,659 | 12,606,000 |
kWh
|
$0.043 |
| Electricity Demand | $337,002 | 28,970 |
kW-mo/yr
|
$11.63 |
| Electricity Fees | $981 | - |
|
- |
| Natural Gas | $397,171 | 77,268 |
MMBtu
|
$5.14 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $64,759 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $14,713 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.1242: Minimize boiler blowdown with better feedwater treatment | $1,293 | $200 | - | - | - |
$993
-
MMBtu
|
- | $300 | |
| 02 | 2.2628: Utilize a less expensive cooling method | $14,010 | $20,000 |
$9,649
224,928
kWh
|
$4,361
-
kW-mo/yr
|
- | - | - | - | |
| 03 | 2.2437: Recover waste heat from equipment | $33,641 | $67,830 | - | - | - |
$33,641
-
MMBtu
|
- | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,186 | $100 |
$4,839
112,795
kWh
|
$2,187
-
kW-mo/yr
|
- | - | $(-600.0) | $(-240.0) | |
| 05 | 2.4224: Upgrade controls on compressors | $1,108 | $100 |
$763
17,784
kWh
|
$345
-
kW-mo/yr
|
- | - | - | - | |
| 06 | 2.3132: Recharge batteries on during off-peak demand periods | $1,874 | $200 | - |
$887
-
kW-mo/yr
|
$987 | - | - | - | |
| 07 | 2.7111: Reduce illumination to minimum necessary levels | $1,993 | $319 |
$1,189
27,720
kWh
|
$538
-
kW-mo/yr
|
- | - | - | $266 | |
| 08 | 2.7135: Install occupancy sensors | $2,395 | $1,909 |
$2,395
55,836
kWh
|
- | - | - | - | - | |
| 09 | 2.4151: Develop a repair/replace policy | $2,259 | $4,256 |
$1,556
36,266
kWh
|
$703
-
kW-mo/yr
|
- | - | - | - | |
| TOTAL RECOMMENDED | $64,759 | $94,914 |
$20,391
475,329
kWh
|
$9,021
-
kW-mo/yr
|
$987 |
$34,634
-
MMBtu
|
$(-600.0) | $326 | ||
| TOTAL IMPLEMENTED | $14,713 | $5,175 |
$8,347
194,565
kWh
|
$4,660
-
kW-mo/yr
|
$987 |
$993
-
MMBtu
|
$(-600.0) | $326 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs