Assessment Year | 2003 |
---|---|
Principal Product | Roasted In-shell Peanuts |
NAICS | 326111: Plastics Bag and Pouch Manufacturing |
SIC | 2068: Salted and Roasted Nuts and Seeds |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
42,500
ft2
|
Annual Production | 35,000,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $46,046 | 1,309,170 |
kWh
|
$0.035 |
Electricity Demand | $32,116 | 2,986 |
kW-mo/yr
|
$10.76 |
Electricity Fees | $3,229 | - |
|
- |
LPG | $249,945 | 40,134 |
MMBtu
|
$6.23 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $49,427 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $396 | $208 |
$218
6,192
kWh
|
$178
-
kW-mo/yr
|
- | |
02 | 2.2443: Re-use or recycle hot or cold process exhaust air | $19,437 | $8,000 | - | - |
$19,437
-
MMBtu
|
|
03 | 2.2443: Re-use or recycle hot or cold process exhaust air | $16,074 | $9,000 | - | - |
$16,074
-
MMBtu
|
|
04 | 2.1122: Re-size charging openings or add a movable door on equipment | $606 | $176 | - | - |
$606
-
MMBtu
|
|
05 | 2.7313: Recycle air for heating, ventilation and air conditioning | $11,263 | $16,548 | - | - |
$11,263
-
MMBtu
|
|
06 | 2.7124: Make a practice of turning off lights when not needed | $234 | - |
$234
6,645
kWh
|
- | - | |
07 | 2.4151: Develop a repair/replace policy | $347 | $260 |
$215
6,125
kWh
|
$132
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $264 | $252 |
$164
4,652
kWh
|
$100
-
kW-mo/yr
|
- | |
09 | 2.7134: Use photocell controls | $806 | $550 |
$328
9,330
kWh
|
$478
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $49,427 | $34,994 |
$1,159
32,944
kWh
|
$888
-
kW-mo/yr
|
$47,380
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs