Assessment Year | 2001 |
---|---|
Principal Product | Phone cable |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 475 |
Plant Area |
500,000
ft2
|
Annual Production | 35,900,000
thousand feet
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $868,921 | 36,138,000 |
kWh
|
$0.024 |
Electricity Demand | $851,872 | 59,726 |
kW-mo/yr
|
$14.26 |
Electricity Fees | $77,282 | - |
|
- |
Natural Gas | $86,642 | 9,294 |
MMBtu
|
$9.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $136,519 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4151: Develop a repair/replace policy | $10,828 | $12,834 |
$5,866
244,432
kWh
|
$4,962
-
kW-mo/yr
|
- | - | - | |
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $3,348 | $500 |
$17,440
726,600
kWh
|
$14,800
-
kW-mo/yr
|
$(-28,892.0)
-
MMBtu
|
- | - | |
03 | 2.2511: Insulate bare equipment | $2,071 | $407 |
$1,142
47,583
kWh
|
$929
-
kW-mo/yr
|
- | - | - | |
04 | 2.2136: Install / repair insulation on steam lines | $1,800 | $400 |
$993
41,371
kWh
|
$807
-
kW-mo/yr
|
- | - | - | |
05 | 2.2511: Insulate bare equipment | $1,122 | $2,225 |
$607
25,310
kWh
|
$515
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $279 | $150 |
$154
6,423
kWh
|
$125
-
kW-mo/yr
|
- | - | - | |
07 | 2.4237: Substitute compressed air cooling with water or air cooling | $23,668 | $26,000 |
$12,802
533,400
kWh
|
$10,866
-
kW-mo/yr
|
- | - | - | |
08 | 2.7251: Reduce air conditioning load by evaporating water from roof | $93,403 | $(-312,000.0) |
$21,072
877,998
kWh
|
$52,986
-
kW-mo/yr
|
- |
$(-6,655.0)
-
Tgal
|
$26,000 | |
TOTAL RECOMMENDED | $136,519 | $(-269,484.0) |
$60,076
2,503,117
kWh
|
$85,990
-
kW-mo/yr
|
$(-28,892.0)
-
MMBtu
|
$(-6,655.0)
-
Tgal
|
$26,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs