| Assessment Year | 2014 |
|---|---|
| Principal Product | Bakery Products |
| NAICS | 311813: Frozen Cakes, Pies, and Other Pastries Manufacturing |
| SIC | 2045: Prepared Flour Mixes and Doughs |
| Sales Range | $5 M to 10M |
| # of Employees | 235 |
| Plant Area |
109,000
ft2
|
| Annual Production | 3,300,600
lb
|
| Production Hrs. Annual | 8,112
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $791,065 | 14,006,894 |
kWh
|
$0.056 |
| Electricity Demand | $72,985 | 26,735 |
kW-mo/yr
|
$2.73 |
| Natural Gas | $136,148 | 54,614 |
MMBtu
|
$2.49 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $84,558 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $83,221 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $23,514 | $71,320 |
$21,932
391,638
kWh
|
$1,582
-
kW-mo/yr
|
- | |
| 02 | 2.4221: Install compressor air intakes in coolest locations | $3,480 | $2,000 |
$3,480
62,135
kWh
|
- | - | |
| 03 | 2.6127: Maintain air filters by cleaning or replacement | $1,460 | $400 |
$1,460
26,066
kWh
|
- | - | |
| 04 | 2.2437: Recover waste heat from equipment | $2,886 | $4,400 | - | - |
$2,886
-
MMBtu
|
|
| 05 | 2.2515: Use optimum thickness insulation | $9,068 | $30,128 |
$9,068
161,929
kWh
|
- | - | |
| 06 | 2.1131: Repair faulty insulation in furnaces, boilers, etc | $1,337 | $676 |
$1,337
23,880
kWh
|
- | - | |
| 07 | 2.4133: Use most efficient type of electric motors | $31,514 | $141,366 |
$29,541
527,526
kWh
|
$1,973
-
kW-mo/yr
|
- | |
| 08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $11,299 | $10,282 |
$11,299
201,766
kWh
|
- | - | |
| TOTAL RECOMMENDED | $84,558 | $260,572 |
$78,117
1,394,940
kWh
|
$3,555
-
kW-mo/yr
|
$2,886
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $83,221 | $259,896 |
$76,780
1,371,060
kWh
|
$3,555
-
kW-mo/yr
|
$2,886
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs