| Assessment Year | 2026 |
|---|---|
| Principal Product | Molding and Injection Parts and Machines |
| NAICS | 333249: Other Industrial Machinery Manufacturing |
| SIC | 3559: Special Industry Machinery, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 180 |
| Plant Area |
333,000
ft2
|
| Annual Production | 6,181
units
|
| Production Hrs. Annual | 4,959
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $251,796 | 2,842,231 |
kWh
|
$0.089 |
| Electricity Demand | $33,606 | 9,745 |
kW-mo/yr
|
$3.45 |
| Electricity Fees | $54,530 | - |
|
- |
| Natural Gas | $94,369 | 14,247 |
MMBtu
|
$6.62 |
| Other Gas | $10,345 | 1 |
MMBtu
|
$10,345.00 |
| TOTAL YEARLY COSTS | $444,646 | |||
| RECOMMENDED SAVINGS* | $65,337 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7261: Install timers and/or thermostats | $47,502 | $85 |
$342
3,838
kWh
|
$176
-
kW-mo/yr
|
- |
$46,984
-
MMBtu
|
|
| 02 | 2.7135: Install occupancy sensors | $5,702 | $1,176 |
$5,212
58,556
kWh
|
$491
-
kW-mo/yr
|
- | - | |
| 03 | 2.3132: Recharge batteries on during off-peak demand periods | $253 | $345 | - | - | $253 | - | |
| 04 | 2.3212: Optimize plant power factor | $5,236 | $38,117 | - | - | $5,236 | - | |
| 05 | 2.4322: Use or replace with energy efficient substitutes | $75 | $650 |
$74
837
kWh
|
$0.0
-
kW-mo/yr
|
- | - | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $896 | - |
$819
9,202
kWh
|
$77
-
kW-mo/yr
|
- | - | |
| 07 | 2.6218: Turn off equipment when not in use | $3,495 | - |
$3,319
37,293
kWh
|
$176
-
kW-mo/yr
|
- | - | |
| 08 | 2.7124: Make a practice of turning off lights when not needed | $35 | $84 |
$32
364
kWh
|
$3
-
kW-mo/yr
|
- | - | |
| 09 | 2.7134: Use photocell controls | $237 | $360 |
$198
2,223
kWh
|
$39
-
kW-mo/yr
|
- | - | |
| 10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $49 | $176 |
$47
526
kWh
|
$2
-
kW-mo/yr
|
- | - | |
| 11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,384 | $248 |
$1,155
12,973
kWh
|
$229
-
kW-mo/yr
|
- | - | |
| 12 | 2.7221: Lower temperature during the winter season and vice-versa | $160 | - | - | - | - |
$160
-
MMBtu
|
|
| 13 | 2.7444: Close holes and openings in building such as broken windows | $311 | $91 | - | - | - |
$311
-
MMBtu
|
|
| TOTAL RECOMMENDED | $65,337 | $41,332 |
$11,197
125,812
kWh
|
$1,195
-
kW-mo/yr
|
$5,489 |
$47,456
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs