Assessment Year 2025
Principal Product sealant and adhesives)
NAICS 325520: Adhesive Manufacturing
SIC 2891: Adhesives and Sealants
Sales Range $50
M
to 100
M
# of Employees 253
Plant Area 290,000
ft2
Annual Production 12,260
ton
Production Hrs. Annual 6,240
hrs
Location (State) Michigan

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $425,085 12,374,185
kWh
Electricity Demand $823,803 25,678
kW-mo/yr
Electricity Fees $23,606 -
Natural Gas $229,860 33,576
MMBtu
TOTAL YEARLY COSTS $1,502,354
RECOMMENDED SAVINGS* $344,066 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.1321: Replace fossil fuel equipment with electrical equipment $66,662 $280,000 $19,132
217,728
kWh
- - $47,530
02 2.2437: Recover waste heat from equipment $7,457 $1,690 $3,030
100,988
kWh
$4,427
-
kW-mo/yr
- -
03 2.3132: Recharge batteries on during off-peak demand periods $5,105 $1,035 - - - $5,105
04 2.4221: Install compressor air intakes in coolest locations $6,871 - $2,248
74,933
kWh
$4,623
-
kW-mo/yr
- -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $774 $50 $312
10,390
kWh
$462
-
kW-mo/yr
- -
06 2.4322: Use or replace with energy efficient substitutes $23,749 $28,860 - - $23,749
-
MMBtu
-
07 2.4322: Use or replace with energy efficient substitutes $80,013 $95,940 - - $80,013
-
MMBtu
-
08 2.4322: Use or replace with energy efficient substitutes $67,736 $100,000 $18,974
632,471
kWh
$48,762
-
kW-mo/yr
- -
09 2.6125: Keep equipment clean $1,263 - $512
17,082
kWh
$751
-
kW-mo/yr
- -
10 2.6211: Conserve energy by efficient use of vending machines $517 $34 $132
4,406
kWh
$385
-
kW-mo/yr
- -
11 2.6218: Turn off equipment when not in use $11,359 - $1,863
62,097
kWh
$9,496
-
kW-mo/yr
- -
12 2.6218: Turn off equipment when not in use $2,961 - $972
32,405
kWh
$1,989
-
kW-mo/yr
- -
13 2.7111: Reduce illumination to minimum necessary levels $116 - $16
541
kWh
$100
-
kW-mo/yr
- -
14 2.7142: Utilize higher efficiency lamps and/or ballasts $533 $3 $82
2,744
kWh
$451
-
kW-mo/yr
- -
15 2.7135: Install occupancy sensors $327 $140 $50
1,648
kWh
$277
-
kW-mo/yr
- -
16 2.7142: Utilize higher efficiency lamps and/or ballasts $54 $215 $22
744
kWh
$32
-
kW-mo/yr
- -
17 2.7224: Reduce space conditioning during non-working hours $3,384 - - - $3,384
-
MMBtu
-
18 2.7444: Close holes and openings in building such as broken windows $703 - - - $703
-
MMBtu
-
19 2.9114: Use solar heat to make electricty $64,482 $467,600 $21,097
703,258
kWh
$43,385
-
kW-mo/yr
- -
TOTAL RECOMMENDED $344,066 $975,567 $68,442
1,861,435
kWh
$115,140
-
kW-mo/yr
$107,849
-
MMBtu
$52,635
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs