Assessment Year | 2025 |
---|---|
Principal Product | sealant and adhesives) |
NAICS | 325520: Adhesive Manufacturing |
SIC | 2891: Adhesives and Sealants |
Sales Range | $50 M to 100M |
# of Employees | 253 |
Plant Area |
290,000
ft2
|
Annual Production | 12,260
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $425,085 | 12,374,185 |
kWh
|
$0.034 |
Electricity Demand | $823,803 | 25,678 |
kW-mo/yr
|
$32.08 |
Electricity Fees | $23,606 | - |
|
- |
Natural Gas | $229,860 | 33,576 |
MMBtu
|
$6.85 |
TOTAL YEARLY COSTS | $1,502,354 | |||
RECOMMENDED SAVINGS* | $344,066 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1321: Replace fossil fuel equipment with electrical equipment | $66,662 | $280,000 |
$19,132
217,728
kWh
|
- | - | $47,530 | |
02 | 2.2437: Recover waste heat from equipment | $7,457 | $1,690 |
$3,030
100,988
kWh
|
$4,427
-
kW-mo/yr
|
- | - | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $5,105 | $1,035 | - | - | - | $5,105 | |
04 | 2.4221: Install compressor air intakes in coolest locations | $6,871 | - |
$2,248
74,933
kWh
|
$4,623
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $774 | $50 |
$312
10,390
kWh
|
$462
-
kW-mo/yr
|
- | - | |
06 | 2.4322: Use or replace with energy efficient substitutes | $23,749 | $28,860 | - | - |
$23,749
-
MMBtu
|
- | |
07 | 2.4322: Use or replace with energy efficient substitutes | $80,013 | $95,940 | - | - |
$80,013
-
MMBtu
|
- | |
08 | 2.4322: Use or replace with energy efficient substitutes | $67,736 | $100,000 |
$18,974
632,471
kWh
|
$48,762
-
kW-mo/yr
|
- | - | |
09 | 2.6125: Keep equipment clean | $1,263 | - |
$512
17,082
kWh
|
$751
-
kW-mo/yr
|
- | - | |
10 | 2.6211: Conserve energy by efficient use of vending machines | $517 | $34 |
$132
4,406
kWh
|
$385
-
kW-mo/yr
|
- | - | |
11 | 2.6218: Turn off equipment when not in use | $11,359 | - |
$1,863
62,097
kWh
|
$9,496
-
kW-mo/yr
|
- | - | |
12 | 2.6218: Turn off equipment when not in use | $2,961 | - |
$972
32,405
kWh
|
$1,989
-
kW-mo/yr
|
- | - | |
13 | 2.7111: Reduce illumination to minimum necessary levels | $116 | - |
$16
541
kWh
|
$100
-
kW-mo/yr
|
- | - | |
14 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $533 | $3 |
$82
2,744
kWh
|
$451
-
kW-mo/yr
|
- | - | |
15 | 2.7135: Install occupancy sensors | $327 | $140 |
$50
1,648
kWh
|
$277
-
kW-mo/yr
|
- | - | |
16 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $54 | $215 |
$22
744
kWh
|
$32
-
kW-mo/yr
|
- | - | |
17 | 2.7224: Reduce space conditioning during non-working hours | $3,384 | - | - | - |
$3,384
-
MMBtu
|
- | |
18 | 2.7444: Close holes and openings in building such as broken windows | $703 | - | - | - |
$703
-
MMBtu
|
- | |
19 | 2.9114: Use solar heat to make electricty | $64,482 | $467,600 |
$21,097
703,258
kWh
|
$43,385
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $344,066 | $975,567 |
$68,442
1,861,435
kWh
|
$115,140
-
kW-mo/yr
|
$107,849
-
MMBtu
|
$52,635 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs