Assessment Year | 2024 |
---|---|
Principal Product | light products and simple furniture products |
NAICS | 335122: Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing |
SIC | 3648: Lighting Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 79 |
Plant Area |
100,000
ft2
|
Annual Production | 200,000
units
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $71,756 | 851,106 |
kWh
|
$0.084 | |
Electricity Demand | $14,450 | 3,083 |
kW-mo/yr
|
$4.69 | |
Electricity Fees | $21,980 | - |
|
- | |
Natural Gas | $52,352 | 6,075 |
MMBtu
|
$8.62 | |
Waste Disposal Costs | |||||
Water Usage | $11,968 | 1,674 |
Tgal
|
$7.15 | |
TOTAL YEARLY COSTS | $172,506 | ||||
RECOMMENDED SAVINGS* | $87,147 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $3,562 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $465 | $484 | - | - |
$465
-
MMBtu
|
- | |
02 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $7,422 | $9,923 | - | - |
$7,422
-
MMBtu
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,153 | - |
$995
12,438
kWh
|
$158
-
kW-mo/yr
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $340 | $2,498 |
$293
3,660
kWh
|
$47
-
kW-mo/yr
|
- | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $160 | $17 |
$153
1,914
kWh
|
$7
-
kW-mo/yr
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $814 | - |
$702
8,775
kWh
|
$112
-
kW-mo/yr
|
- | - | |
07 | 2.4322: Use or replace with energy efficient substitutes | $320 | $1,932 |
$87
1,082
kWh
|
$234
-
kW-mo/yr
|
- | - | |
08 | 2.6218: Turn off equipment when not in use | $426 | - |
$395
4,935
kWh
|
$32
-
kW-mo/yr
|
- | - | |
09 | 2.7134: Use photocell controls | $74 | $706 |
$64
796
kWh
|
$10
-
kW-mo/yr
|
- | - | |
10 | 2.7444: Close holes and openings in building such as broken windows | $844 | $555 | - | - |
$844
-
MMBtu
|
- | |
11 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $1,303 | $13,605 | - | - |
$1,303
-
MMBtu
|
- | |
12 | 2.8121: Apply for tax-free status for energy purchases | $3,810 | - | - | - | - | $3,810 | |
13 | 2.9114: Use solar heat to make electricty | $70,016 | $432,400 |
$70,016
833,528
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $87,147 | $462,120 |
$72,704
867,127
kWh
|
$600
-
kW-mo/yr
|
$10,033
-
MMBtu
|
$3,810 | ||
TOTAL IMPLEMENTED | $3,562 | $16,744 |
$1,400
17,501
kWh
|
$394
-
kW-mo/yr
|
$1,768
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs