Assessment Year | 2023 |
---|---|
Principal Product | Motor vehicle metal stamping products |
NAICS | 336370: Motor Vehicle Metal Stamping |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 90 |
Plant Area |
335,000
ft2
|
Annual Production | 5,990,400
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Michigan |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $212,854 | 3,874,107 |
kWh
|
$0.055 |
Electricity Demand | $143,410 | 8,982 |
kW-mo/yr
|
$15.97 |
Electricity Fees | $34,386 | - |
|
- |
Natural Gas | $95,490 | 11,184 |
MMBtu
|
$8.54 |
TOTAL YEARLY COSTS | $486,140 | |||
RECOMMENDED SAVINGS* | $84,265 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,118 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $116 | $319 |
$116
2,315
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,700 | $7,887 |
$998
19,950
kWh
|
$1,702
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,957 | $2,281 |
$1,289
25,778
kWh
|
$668
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $228 | $480 |
$151
3,013
kWh
|
$77
-
kW-mo/yr
|
- | |
05 | 2.6125: Keep equipment clean | $33 | - |
$22
440
kWh
|
$11
-
kW-mo/yr
|
- | |
06 | 2.7243: Improve air circulation with destratification fans / other methods | $20,803 | $28,063 | - | - |
$20,803
-
MMBtu
|
|
07 | 2.7444: Close holes and openings in building such as broken windows | $54 | $51 | - | - |
$54
-
MMBtu
|
|
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $39,395 | $128,601 | - | - |
$39,395
-
MMBtu
|
|
09 | 2.9114: Use solar heat to make electricty | $18,979 | $158,490 |
$9,157
183,139
kWh
|
$9,822
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $84,265 | $326,172 |
$11,732
234,635
kWh
|
$12,280
-
kW-mo/yr
|
$60,252
-
MMBtu
|
||
TOTAL IMPLEMENTED | $21,118 | $28,594 |
$173
3,453
kWh
|
$88
-
kW-mo/yr
|
$20,857
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs