Assessment Year | 2004 |
---|---|
Principal Product | Agricultural Pesticides |
NAICS | 325320: Pesticide and Other Agricultural Chemical Manufacturing |
SIC | 2879: Pesticides and Agricultural Chemicals, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 120 |
Plant Area |
239,000
ft2
|
Annual Production | 8,750
Tgal
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $231,065 | 5,146,020 |
kWh
|
$0.045 |
Electricity Demand | $43,350 | 13,347 |
kW-mo/yr
|
$3.25 |
Electricity Fees | $74,051 | - |
|
- |
Natural Gas | $184,454 | 23,835 |
MMBtu
|
$7.74 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $108,549 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $27,618 | $3,865 | - | - | - |
$27,618
-
MMBtu
|
|
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $17,390 | $2,000 | - | - | - |
$17,390
-
MMBtu
|
|
03 | 2.2121: Increase amount of condensate returned | $17,029 | $5,830 | - | - | - |
$17,029
-
MMBtu
|
|
04 | 2.2414: Use waste heat from hot flue gases to preheat | $10,838 | $7,618 | - | - | - |
$10,838
-
MMBtu
|
|
05 | 2.2511: Insulate bare equipment | $9,148 | $698 | - | - | - |
$9,148
-
MMBtu
|
|
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $8,547 | $28,092 |
$5,146
120,137
kWh
|
- | $3,401 | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,220 | $400 |
$4,950
115,552
kWh
|
- | $3,270 | - | |
08 | 2.7111: Reduce illumination to minimum necessary levels | $4,706 | $211 |
$2,153
50,269
kWh
|
$927
-
kW-mo/yr
|
$1,626 | - | |
09 | 2.7134: Use photocell controls | $2,197 | $556 |
$1,323
30,877
kWh
|
- | $874 | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,287 | $1,192 |
$712
16,616
kWh
|
$86
-
kW-mo/yr
|
$489 | - | |
11 | 2.7261: Install timers and/or thermostats | $917 | $236 |
$552
12,889
kWh
|
- | $365 | - | |
12 | 2.2136: Install / repair insulation on steam lines | $652 | $432 | - | - | - |
$652
-
MMBtu
|
|
TOTAL RECOMMENDED | $108,549 | $51,130 |
$14,836
346,340
kWh
|
$1,013
-
kW-mo/yr
|
$10,025 |
$82,675
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs