Assessment Year | 2004 |
---|---|
Principal Product | pvc pipe |
NAICS | 326122: Plastics Pipe and Pipe Fitting Manufacturing |
SIC | 3084: Plastics Pipe |
Sales Range | $10 M to 50M |
# of Employees | 83 |
Plant Area |
105,000
ft2
|
Annual Production | 120,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $625,077 | 18,387,900 |
kWh
|
$0.034 |
Electricity Demand | $291,181 | 31,610 |
kW-mo/yr
|
$9.21 |
Electricity Fees | $26,427 | - |
|
- |
Natural Gas | $17,261 | 1,944 |
MMBtu
|
$8.88 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $109,919 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $80,970 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $54,067 | $26,100 | - | - | $54,067 | - | - | |
02 | 3.4154: Eliminate leaks in water lines and valves | $19,536 | $250 | - | - | - | - |
$19,536
-
Tgal
|
|
03 | 2.2437: Recover waste heat from equipment | $12,086 | $1,814 | - | - | - |
$12,086
-
MMBtu
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,838 | $14,639 |
$5,850
163,076
kWh
|
$2,858
-
kW-mo/yr
|
$130 | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,879 | $708 |
$6,778
188,961
kWh
|
- | $101 | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $2,388 | $358 |
$1,424
39,700
kWh
|
$928
-
kW-mo/yr
|
$36 | - | - | |
07 | 2.3132: Recharge batteries on during off-peak demand periods | $2,064 | - | - |
$2,034
-
kW-mo/yr
|
$30 | - | - | |
08 | 2.7261: Install timers and/or thermostats | $1,547 | $827 |
$1,524
42,482
kWh
|
- | $23 | - | - | |
09 | 2.8112: Combine utility meters | $1,077 | - | - | - | $1,077 | - | - | |
10 | 2.7135: Install occupancy sensors | $949 | $519 |
$903
17,755
kWh
|
- | $46 | - | - | |
11 | 2.4133: Use most efficient type of electric motors | $488 | $820 |
$481
13,414
kWh
|
- | $7 | - | - | |
TOTAL RECOMMENDED | $109,919 | $46,035 |
$16,960
465,388
kWh
|
$5,820
-
kW-mo/yr
|
$55,517 |
$12,086
-
MMBtu
|
$19,536
-
Tgal
|
||
TOTAL IMPLEMENTED | $80,970 | $27,878 |
$7,259
202,375
kWh
|
- | $54,175 | - |
$19,536
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs