Assessment Year | 1994 |
---|---|
Principal Product | weather seals |
NAICS |
n/a
|
SIC | 3069: Fabricated Rubber Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 319 |
Plant Area |
96,000
ft2
|
Annual Production | 9,000,000
lb
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $432,771 | 8,391,559 |
kWh
|
$0.052 |
Natural Gas | $94,052 | 23,876 |
MMBtu
|
$3.94 |
LPG | $25,251 | 4,987 |
MMBtu
|
$5.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $53,496 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,877 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $5,154 | $2,340 |
$5,154
99,941
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,966 | $15,637 |
$4,966
96,424
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,202 | $611 |
$2,202
42,790
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $266 | $760 |
$266
5,275
kWh
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $4,564 | $2,374 |
$4,564
88,511
kWh
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,947 | $100 |
$4,947
95,838
kWh
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $3,518 | $12,983 |
$3,518
68,288
kWh
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $716 | $695 |
$716
13,775
kWh
|
- | |
09 | 2.7444: Close holes and openings in building such as broken windows | $1,611 | $50 | - |
$1,611
-
MMBtu
|
|
10 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $857 | $1,057 |
$1,192
23,154
kWh
|
$(-335.0)
-
MMBtu
|
|
11 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $24,695 | $19,160 |
$36,636
710,727
kWh
|
$(-11,941.0)
-
MMBtu
|
|
TOTAL RECOMMENDED | $53,496 | $55,767 |
$64,161
1,244,723
kWh
|
$(-10,665.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $1,877 | $810 |
$266
5,275
kWh
|
$1,611
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs