ITAC Assessment: MI0411
ITAC logo
ITAC Assessment: MI0411
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2022
Principal Product Beverages
NAICS 312111: Soft Drink Manufacturing
SIC 2086: Bottled and Canned Soft Drinks and Carbonated Waters
Sales Range $100
M
to 500
M
# of Employees 230
Plant Area 183,000
ft2
Annual Production 16,000,000
pieces
Production Hrs. Annual 8,736
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $528,704 8,876,172
kWh
Electricity Demand $277,860 19,248
kW-mo/yr
Electricity Fees $142,574 -
Waste Disposal Costs
Water Usage $1,515,852 161,556
Tgal
TOTAL YEARLY COSTS $2,464,990
RECOMMENDED SAVINGS* $100,277 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $28,701

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.7232: Replace existing hvac unit with high efficiency model $59,622 $102,900 $50,267
837,782
kWh
$9,355
-
kW-mo/yr
-
02 2.7221: Lower temperature during the winter season and vice-versa $15,400 $630 $11,574
192,900
kWh
$3,826
-
kW-mo/yr
-
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $6,210 $1,650 $5,030
83,833
kWh
$1,660
-
kW-mo/yr
$(-480.0)
04 2.7425: Clean or color roof to reduce solar load $5,960 $7,503 $2,669
44,483
kWh
$3,291
-
kW-mo/yr
-
05 2.7447: Install vinyl strip / high speed / air curtain doors $5,123 $1,040 $3,853
64,209
kWh
$1,270
-
kW-mo/yr
-
06 2.7124: Make a practice of turning off lights when not needed $4,028 - $3,812
63,541
kWh
$1,256
-
kW-mo/yr
$(-1,040.0)
07 2.4226: Use / purchase optimum sized compressor $3,063 $27,147 $2,298
38,307
kWh
$765
-
kW-mo/yr
-
08 2.4221: Install compressor air intakes in coolest locations $871 $1,462 $654
10,892
kWh
$217
-
kW-mo/yr
-
TOTAL RECOMMENDED $100,277 $142,332 $80,157
1,335,947
kWh
$21,640
-
kW-mo/yr
$(-1,520.0)
TOTAL IMPLEMENTED $28,701 $29,427 $22,714
378,581
kWh
$7,507
-
kW-mo/yr
$(-1,520.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs