| Assessment Year | 2022 |
|---|---|
| Principal Product | Beverages |
| NAICS | 312111: Soft Drink Manufacturing |
| SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
| Sales Range | $100 M to 500M |
| # of Employees | 230 |
| Plant Area |
183,000
ft2
|
| Annual Production | 16,000,000
pieces
|
| Production Hrs. Annual | 8,736
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $528,704 | 8,876,172 |
kWh
|
$0.060 | |
| Electricity Demand | $277,860 | 19,248 |
kW-mo/yr
|
$14.44 | |
| Electricity Fees | $142,574 | - |
|
- | |
| Waste Disposal Costs | |||||
| Water Usage | $1,515,852 | 161,556 |
Tgal
|
$9.38 | |
| TOTAL YEARLY COSTS | $2,464,990 | ||||
| RECOMMENDED SAVINGS* | $100,277 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $28,701 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $59,622 | $102,900 |
$50,267
837,782
kWh
|
$9,355
-
kW-mo/yr
|
- | |
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $15,400 | $630 |
$11,574
192,900
kWh
|
$3,826
-
kW-mo/yr
|
- | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,210 | $1,650 |
$5,030
83,833
kWh
|
$1,660
-
kW-mo/yr
|
$(-480.0) | |
| 04 | 2.7425: Clean or color roof to reduce solar load | $5,960 | $7,503 |
$2,669
44,483
kWh
|
$3,291
-
kW-mo/yr
|
- | |
| 05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $5,123 | $1,040 |
$3,853
64,209
kWh
|
$1,270
-
kW-mo/yr
|
- | |
| 06 | 2.7124: Make a practice of turning off lights when not needed | $4,028 | - |
$3,812
63,541
kWh
|
$1,256
-
kW-mo/yr
|
$(-1,040.0) | |
| 07 | 2.4226: Use / purchase optimum sized compressor | $3,063 | $27,147 |
$2,298
38,307
kWh
|
$765
-
kW-mo/yr
|
- | |
| 08 | 2.4221: Install compressor air intakes in coolest locations | $871 | $1,462 |
$654
10,892
kWh
|
$217
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $100,277 | $142,332 |
$80,157
1,335,947
kWh
|
$21,640
-
kW-mo/yr
|
$(-1,520.0) | ||
| TOTAL IMPLEMENTED | $28,701 | $29,427 |
$22,714
378,581
kWh
|
$7,507
-
kW-mo/yr
|
$(-1,520.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs