Assessment Year | 2020 |
---|---|
Principal Product | Patio Furniture & Furniture Parts |
NAICS | 337215: Showcase, Partition, Shelving, and Locker Manufacturing |
SIC | 2511: Wood Household Furniture, Except Upholstered |
Sales Range | $50 M to 100M |
# of Employees | 250 |
Plant Area |
200,000
ft2
|
Annual Production | 70,000,000
pieces
|
Production Hrs. Annual | 4,335
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $116,031 | 2,530,400 |
kWh
|
$0.046 |
Electricity Demand | $83,470 | 6,471 |
kW-mo/yr
|
$12.90 |
Electricity Fees | $44,165 | - |
|
- |
Natural Gas | $81,861 | 6,910 |
MMBtu
|
$11.85 |
TOTAL YEARLY COSTS | $325,527 | |||
RECOMMENDED SAVINGS* | $62,508 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,326 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7425: Clean or color roof to reduce solar load | $15,466 | $26,940 |
$4,837
105,152
kWh
|
$10,629
-
kW-mo/yr
|
- | |
02 | 2.7232: Replace existing hvac unit with high efficiency model | $10,944 | $53,621 |
$7,758
168,656
kWh
|
$3,186
-
kW-mo/yr
|
- | |
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $8,446 | $2,260 |
$(-46.0)
(-999)
kWh
|
$(-52.0)
-
kW-mo/yr
|
$8,544
-
MMBtu
|
|
04 | 2.4224: Upgrade controls on compressors | $7,381 | $10,120 |
$5,304
115,304
kWh
|
$2,077
-
kW-mo/yr
|
- | |
05 | 2.7224: Reduce space conditioning during non-working hours | $4,983 | $580 |
$4,983
108,328
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,663 | $120 |
$3,360
73,044
kWh
|
$1,303
-
kW-mo/yr
|
- | |
07 | 2.6218: Turn off equipment when not in use | $4,066 | $480 |
$4,066
88,382
kWh
|
- | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,834 | $1,980 |
$2,047
44,499
kWh
|
$787
-
kW-mo/yr
|
- | |
09 | 2.7221: Lower temperature during the winter season and vice-versa | $1,780 | $580 |
$1,277
27,768
kWh
|
$503
-
kW-mo/yr
|
- | |
10 | 2.7135: Install occupancy sensors | $1,149 | $500 |
$1,149
24,970
kWh
|
- | - | |
11 | 2.7444: Close holes and openings in building such as broken windows | $796 | $134 |
$435
9,460
kWh
|
$361
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $62,508 | $97,315 |
$35,170
764,564
kWh
|
$18,794
-
kW-mo/yr
|
$8,544
-
MMBtu
|
||
TOTAL IMPLEMENTED | $18,326 | $3,740 |
$15,733
342,021
kWh
|
$2,593
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs