| Assessment Year | 2019 |
|---|---|
| Principal Product | Electrical and Fiber Optics Connectors |
| NAICS | 334417: Electronic Connector Manufacturing |
| SIC | 3678: Electronic Connectors |
| Sales Range | $100 M to 500M |
| # of Employees | 345 |
| Plant Area |
156,000
ft2
|
| Annual Production | 9,600
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Florida |
| View Case Study | |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $126,484 | 2,840,160 |
kWh
|
$0.045 |
| Electricity Demand | $78,027 | 5,863 |
kW-mo/yr
|
$13.31 |
| Electricity Fees | $37,071 | - |
|
- |
| TOTAL YEARLY COSTS | $241,582 | |||
| RECOMMENDED SAVINGS* | $79,804 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $53,230 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7232: Replace existing hvac unit with high efficiency model | $20,647 | $100,030 |
$14,685
326,339
kWh
|
$5,962
-
kW-mo/yr
|
|
| 02 | 2.7252: Utilize an evaporative air pre-cooler or other heat exchanger in ac system | $18,921 | $27,048 |
$13,451
298,902
kWh
|
$5,470
-
kW-mo/yr
|
|
| 03 | 2.6218: Turn off equipment when not in use | $17,548 | $3,600 |
$17,548
389,952
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,278 | $17,214 |
$7,192
159,819
kWh
|
$4,086
-
kW-mo/yr
|
|
| 05 | 2.7229: Air condition only space necessary | $5,773 | $9,476 |
$4,109
91,315
kWh
|
$1,664
-
kW-mo/yr
|
|
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,612 | $160 |
$1,853
41,181
kWh
|
$759
-
kW-mo/yr
|
|
| 07 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,880 | $1,446 |
$1,201
26,699
kWh
|
$679
-
kW-mo/yr
|
|
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,145 | $1,980 |
$812
18,035
kWh
|
$333
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $79,804 | $160,954 |
$60,851
1,352,242
kWh
|
$18,953
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $53,230 | $122,984 |
$42,090
935,326
kWh
|
$11,140
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs