Assessment Year 2015
Principal Product Commercial Impressions
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2752: Commercial Printing, Lithographic
Sales Range $10
M
to 50
M
# of Employees 180
Plant Area 37,500
ft2
Annual Production 24,000,000
units
Production Hrs. Annual 4,160
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $113,408 1,917,810
kWh
Electricity Demand $54,838 5,017
kW-mo/yr
Electricity Fees $25,556 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $48,079 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $24,531

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
01 2.7221: Lower temperature during the winter season and vice-versa $10,332 $40 $8,233
139,540
kWh
$2,099
-
kW-mo/yr
-
02 2.7447: Install vinyl strip / high speed / air curtain doors $7,812 $11,680 $6,227
105,542
kWh
$1,585
-
kW-mo/yr
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $7,148 $18,346 $4,656
78,915
kWh
$2,492
-
kW-mo/yr
-
04 2.7425: Clean or color roof to reduce solar load $6,858 $19,974 $4,497
76,218
kWh
$2,361
-
kW-mo/yr
-
05 2.7111: Reduce illumination to minimum necessary levels $5,588 $1,080 $3,642
61,723
kWh
$1,946
-
kW-mo/yr
-
06 2.6218: Turn off equipment when not in use $5,333 $3,600 $5,333
90,396
kWh
- -
07 2.3132: Recharge batteries on during off-peak demand periods $1,181 $3,140 - $1,181
-
kW-mo/yr
-
08 2.8114: Change rate schedules or other changes in utility service $898 $560 - - $898
09 2.4221: Install compressor air intakes in coolest locations $756 $639 $494
8,366
kWh
$262
-
kW-mo/yr
-
10 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $608 $1,660 $477
8,093
kWh
$131
-
kW-mo/yr
-
11 2.4231: Reduce the pressure of compressed air to the minimum required $480 $40 $349
5,912
kWh
$131
-
kW-mo/yr
-
12 2.7135: Install occupancy sensors $471 $663 $471
7,991
kWh
- -
13 2.2511: Insulate bare equipment $302 $160 $157
2,658
kWh
$145
-
kW-mo/yr
-
14 2.7447: Install vinyl strip / high speed / air curtain doors $222 $706 $143
2,429
kWh
$79
-
kW-mo/yr
-
15 2.8123: Pay utility bills on time $90 $80 - - $90
TOTAL RECOMMENDED $48,079 $62,368 $34,679
587,783
kWh
$12,412
-
kW-mo/yr
$988
TOTAL IMPLEMENTED $24,531 $42,862 $17,799
301,693
kWh
$5,744
-
kW-mo/yr
$988
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs