Assessment Year 2015
Principal Product Newspapers
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2711: Newspapers: Publishing, or Publishing and Printing
Sales Range $100
M
to 500
M
# of Employees 500
Plant Area 328,000
ft2
Annual Production 14,000
ton
Production Hrs. Annual 8,736
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $778,305 9,787,560
kWh
Electricity Demand $258,197 32,767
kW-mo/yr
Electricity Fees $104,646 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $105,488 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $69,945

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
01 2.4231: Reduce the pressure of compressed air to the minimum required $25,305 $11,600 $22,255
281,709
kWh
$3,050
-
kW-mo/yr
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $24,948 $1,660 $21,383
270,673
kWh
$3,565
-
kW-mo/yr
-
03 2.7135: Install occupancy sensors $11,055 $676 $11,055
139,942
kWh
- -
04 2.4231: Reduce the pressure of compressed air to the minimum required $9,296 $40 $8,177
103,500
kWh
$1,119
-
kW-mo/yr
-
05 2.7111: Reduce illumination to minimum necessary levels $6,998 $2,680 $6,076
76,906
kWh
$922
-
kW-mo/yr
-
06 2.3132: Recharge batteries on during off-peak demand periods $6,524 $6,280 - $3,317
-
kW-mo/yr
$3,207
07 2.7229: Air condition only space necessary $5,757 $1,500 $5,064
64,106
kWh
$693
-
kW-mo/yr
-
08 2.6231: Utilize controls to operate equipment only when needed $4,632 $570 $4,632
58,630
kWh
- -
09 2.4239: Eliminate or reduce compressed air usage $4,481 $12,150 $3,941
49,883
kWh
$540
-
kW-mo/yr
-
10 2.7221: Lower temperature during the winter season and vice-versa $3,212 $40 $2,825
35,764
kWh
$387
-
kW-mo/yr
-
11 2.7447: Install vinyl strip / high speed / air curtain doors $1,371 $3,309 $1,206
15,266
kWh
$165
-
kW-mo/yr
-
12 2.7142: Utilize higher efficiency lamps and/or ballasts $1,078 $1,638 $1,078
13,571
kWh
- -
13 2.7124: Make a practice of turning off lights when not needed $831 $20 $729
9,225
kWh
$102
-
kW-mo/yr
-
TOTAL RECOMMENDED $105,488 $42,163 $88,421
1,119,175
kWh
$13,860
-
kW-mo/yr
$3,207
TOTAL IMPLEMENTED $69,945 $16,913 $57,161
723,477
kWh
$9,577
-
kW-mo/yr
$3,207
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs