Assessment Year | 2008 |
---|---|
Principal Product | Medical and Laboratory Plastics |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
47,000
ft2
|
Annual Production | 20,000,000
pieces
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $525,440 | 3,335,267 |
kWh
|
$0.16 |
Electricity Demand | $57,841 | 7,084 |
kW-mo/yr
|
$8.17 |
Electricity Fees | $2,400 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $50,606 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,731 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7221: Lower temperature during the winter season and vice-versa | $21,617 | $120 |
$19,215
147,086
kWh
|
$2,402
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,137 | $1,210 |
$6,743
42,800
kWh
|
$394
-
kW-mo/yr
|
- | |
03 | 2.4323: Use optimum size and capacity equipment | $6,615 | $3,475 |
$6,180
39,229
kWh
|
$435
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,266 | $3,978 |
$4,678
35,808
kWh
|
$588
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,337 | $40 |
$2,994
19,006
kWh
|
$343
-
kW-mo/yr
|
- | |
06 | 2.4221: Install compressor air intakes in coolest locations | $3,238 | $280 |
$2,922
18,549
kWh
|
$316
-
kW-mo/yr
|
- | |
07 | 3.5217: Reuse / recycle/ sell paper products | $1,875 | $120 | - | - | $1,875 | |
08 | 2.7447: Install vinyl strip / high speed / air curtain doors | $1,521 | $480 |
$1,251
16,465
kWh
|
$270
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $50,606 | $9,703 |
$43,983
318,943
kWh
|
$4,748
-
kW-mo/yr
|
$1,875 | ||
TOTAL IMPLEMENTED | $48,731 | $9,583 |
$43,983
318,943
kWh
|
$4,748
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs