Assessment Year | 2004 |
---|---|
Principal Product | Electrical Cables |
NAICS | 335931: Current-Carrying Wiring Device Manufacturing |
SIC | 3643: Current-Carrying Wiring Devices |
Sales Range | $10 M to 50M |
# of Employees | 69 |
Plant Area |
67,000
ft2
|
Annual Production | 200,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $90,563 | 1,801,440 |
kWh
|
$0.050 |
Electricity Demand | $42,914 | 5,332 |
kW-mo/yr
|
$8.05 |
Electricity Fees | $11,260 | - |
|
- |
LPG | $4,920 | 284 |
MMBtu
|
$17.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $125,336 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $32,088 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $2,620 | - | - | - | $2,620 | - | |
02 | 2.6218: Turn off equipment when not in use | $44,199 | - |
$44,199
744,500
kWh
|
- | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $553 | - |
$553
10,479
kWh
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,800 | - |
$1,800
34,133
kWh
|
- | - | - | |
05 | 3.2176: Increase use of automation | $28,521 | - | - | - | - | $28,521 | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,994 | - |
$3,474
65,887
kWh
|
$(-480.0) | - | - | |
07 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $8,755 | $510 |
$8,755
83,211
kWh
|
- | - | - | |
08 | 4.622: Install rotating carousels to reduce set-up times | $23,333 | $21,000 | - | - | - | $23,333 | |
09 | 2.7444: Close holes and openings in building such as broken windows | $12,561 | - |
$12,561
238,764
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $125,336 | $21,510 |
$71,342
1,176,974
kWh
|
$(-480.0) | $2,620 | $51,854 | ||
TOTAL IMPLEMENTED | $32,088 | $21,510 |
$8,755
83,211
kWh
|
- | - | $23,333 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs