Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,731 | 1,176,436 |
kWh
|
$0.075 |
Electricity Demand | $53,231 | 5,344 |
kW-mo/yr
|
$9.96 |
Electricity Fees | $4,590 | - |
|
- |
LPG | $2,403 | 133 |
MMBtu
|
$18.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $15,212 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,294 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,319 | $8,303 |
$1,311
18,757
kWh
|
$1,008
-
kW-mo/yr
|
- | - | - | - | |
02 | 4.231: Purchase equipment instead of leasing | $1,356 | $2,300 |
$(-306.0)
(-4,396)
kWh
|
$(-119.0)
-
kW-mo/yr
|
$1,841 | $(-60.0) | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,066 | $650 |
$1,066
15,240
kWh
|
- | - | - | - | - | |
04 | 2.2135: Repair and eliminate steam leaks | $941 | $500 | - | - | - | - | - | $941 | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $829 | $2,085 |
$829
11,723
kWh
|
- | - | - | - | - | |
06 | 4.821: Pay bills on time to avoid late fees | $655 | - | - | - | $655 | - | - | - | |
07 | 2.4133: Use most efficient type of electric motors | $360 | $190 |
$308
4,396
kWh
|
$52
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $215 | $500 |
$215
3,224
kWh
|
- | - | - | - | - | |
09 | 3.2123: Convert to high volume low pressure (hvlp) paint guns | $6,387 | $1,677 | - | - | - | - | $6,387 | - | |
10 | 3.5313: Increase amount of waste recovered for resale | $1,008 | - | - | - | - | - | $1,008 | - | |
11 | 3.4154: Eliminate leaks in water lines and valves | $76 | $25 | - | - | - | - | - | $76 | |
TOTAL RECOMMENDED | $15,212 | $16,230 |
$3,423
48,944
kWh
|
$941
-
kW-mo/yr
|
$2,496 | $(-60.0) | $7,395 | $1,017 | ||
TOTAL IMPLEMENTED | $11,294 | $13,305 |
$1,220
17,585
kWh
|
$889
-
kW-mo/yr
|
$1,841 | $(-60.0) | $6,387 | $1,017 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs