Assessment Year | 2007 |
---|---|
Principal Product | Automotive timing chains |
NAICS | 333613: Mechanical Power Transmission Equipment Manufacturing |
SIC | 3568: Mechanical Power Transmission Equipment, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 195 |
Plant Area |
230,000
ft2
|
Annual Production | 4,000,000
lb
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $534,502 | 8,764,800 |
kWh
|
$0.061 |
Electricity Demand | $124,164 | 18,766 |
kW-mo/yr
|
$6.62 |
Natural Gas | $102,828 | 8,823 |
MMBtu
|
$11.65 |
LPG | $84,537 | 6,159 |
MMBtu
|
$13.73 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $87,872 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,603 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,636 | $132,834 |
$19,183
231,117
kWh
|
$2,453
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,128 | $3,725 |
$5,438
64,742
kWh
|
$690
-
kW-mo/yr
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $5,603 | $2,550 |
$4,973
59,200
kWh
|
$630
-
kW-mo/yr
|
- | |
04 | 2.2437: Recover waste heat from equipment | $37,450 | $12,998 | - | - |
$37,450
-
MMBtu
|
|
05 | 2.7261: Install timers and/or thermostats | $16,346 | $1,088 |
$2,484
29,573
kWh
|
- |
$13,862
-
MMBtu
|
|
06 | 2.4323: Use optimum size and capacity equipment | $709 | $300 |
$629
7,488
kWh
|
$80
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $87,872 | $153,495 |
$32,707
392,120
kWh
|
$3,853
-
kW-mo/yr
|
$51,312
-
MMBtu
|
||
TOTAL IMPLEMENTED | $5,603 | $2,550 |
$4,973
59,200
kWh
|
$630
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs