Assessment Year | 2002 |
---|---|
Principal Product | Flock fiber |
NAICS |
n/a
|
SIC | 2261: Finishers of Broadwoven Fabrics of Cotton |
Sales Range | $10 M to 50M |
# of Employees | 88 |
Plant Area |
75,000
ft2
|
Annual Production | 9,000,000
lb
|
Production Hrs. Annual | 5,400
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $208,557 | 2,531,400 |
kWh
|
$0.082 |
Electricity Fees | $33,593 | - |
|
- |
Natural Gas | $444,007 | 64,197 |
MMBtu
|
$6.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $226,009 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $165,008 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2444: Use hot process fluids to preheat incoming process fluids | $151,365 | $135,000 |
$(-2,556.0)
(-33,570)
kWh
|
$(-341.0)
-
kW-mo/yr
|
$154,262
-
MMBtu
|
- | |
02 | 3.4151: Minimize water usage | $43,582 | $43,100 |
$(-232.0)
(-3,040)
kWh
|
$(-911.0)
-
kW-mo/yr
|
$21,440
-
MMBtu
|
$23,285
-
Tgal
|
|
03 | 2.2443: Re-use or recycle hot or cold process exhaust air | $14,155 | $19,000 |
$(-3,384.0)
(-50,355)
kWh
|
$(-916.0)
-
kW-mo/yr
|
$18,455
-
MMBtu
|
- | |
04 | 2.2511: Insulate bare equipment | $5,343 | $8,400 | - | - |
$5,343
-
MMBtu
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,745 | $460 |
$3,745
49,191
kWh
|
- | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,589 | $5,200 |
$3,589
47,144
kWh
|
- | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $966 | $625 |
$966
12,682
kWh
|
- | - | - | |
08 | 2.7224: Reduce space conditioning during non-working hours | $560 | - | - | - |
$560
-
MMBtu
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,704 | $15,768 |
$2,704
35,520
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $226,009 | $227,553 |
$4,832
57,572
kWh
|
$(-2,168.0)
-
kW-mo/yr
|
$200,060
-
MMBtu
|
$23,285
-
Tgal
|
||
TOTAL IMPLEMENTED | $165,008 | $149,685 |
$5,744
75,447
kWh
|
$(-341.0)
-
kW-mo/yr
|
$159,605
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs