Assessment Year | 1999 |
---|---|
Principal Product | tape and CD jewel cases |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 52 |
Plant Area |
62,775
ft2
|
Annual Production | 195,000,000
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $175,082 | 3,425,850 |
kWh
|
$0.051 |
Electricity Demand | $97,191 | 6,397 |
kW-mo/yr
|
$15.19 |
Natural Gas | $18,275 | 2,102 |
MMBtu
|
$8.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,507 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,762 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2612: Use cooling tower water instead of refrigeration | $9,010 | $21,612 |
$5,018
121,336
kWh
|
$3,992
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,201 | $18,690 |
$6,201
138,628
kWh
|
- | - | |
03 | 2.7231: Use radiant heater for spot heating | $6,592 | $40,000 |
$1,113
26,964
kWh
|
$97
-
kW-mo/yr
|
$5,382
-
MMBtu
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,735 | $13,320 |
$3,872
94,373
kWh
|
$1,863
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,836 | - |
$2,836
68,581
kWh
|
- | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $703 | $1,451 |
$703
16,999
kWh
|
- | - | |
07 | 2.6231: Utilize controls to operate equipment only when needed | $681 | - |
$681
16,413
kWh
|
- | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $428 | $200 |
$290
7,034
kWh
|
$138
-
kW-mo/yr
|
- | |
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $321 | $30 |
$321
7,913
kWh
|
- | - | |
TOTAL RECOMMENDED | $32,507 | $95,303 |
$21,035
498,241
kWh
|
$6,090
-
kW-mo/yr
|
$5,382
-
MMBtu
|
||
TOTAL IMPLEMENTED | $17,762 | $60,371 |
$12,145
282,532
kWh
|
$235
-
kW-mo/yr
|
$5,382
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs