Assessment Year | 1988 |
---|---|
Principal Product | DECORATIVE WALL COVERING |
NAICS |
n/a
|
SIC | 2679: Converted Paper and Paperboard Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 166 |
Plant Area |
n/a
|
Annual Production | 72,000
thousand feet
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $403,815 | 5,585,873 |
kWh
|
$0.072 |
Natural Gas | $263,326 | 54,978 |
MMBtu
|
$4.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $91,963 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,377 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,207 | $2,710 |
$1,207
18,171
kWh
|
- | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $3,242 | $386 |
$3,242
44,842
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $38,184 | $11,762 |
$38,184
528,136
kWh
|
- | - | |
04 | 2.6232: Install set-back timers | $325 | $446 |
$325
4,396
kWh
|
- | - | |
05 | 2.2122: Install / repair insulation on condensate lines | $872 | $240 | - |
$872
-
MMBtu
|
- | |
06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $21,158 | - |
$21,958
-
kWh
|
- | $(-800.0) | |
07 | 2.7111: Reduce illumination to minimum necessary levels | $170 | - |
$170
2,345
kWh
|
- | - | |
08 | 2.2443: Re-use or recycle hot or cold process exhaust air | $26,805 | $31,196 | - |
$26,805
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $91,963 | $46,740 |
$65,086
597,890
kWh
|
$27,677
-
MMBtu
|
$(-800.0) | ||
TOTAL IMPLEMENTED | $1,377 | $2,710 |
$1,377
20,516
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs