Assessment Year 2017
Principal Product Extruded plastics and injection molding packaging
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 50
Plant Area 229,000
ft2
Annual Production 10,000,000
pieces
Production Hrs. Annual 8,736
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,306,690 18,508,800
kWh
Electricity Demand $173,785 37,213
kW-mo/yr
Electricity Fees $51,904 -
Natural Gas $4,267 498
MMBtu
TOTAL YEARLY COSTS $1,536,646
RECOMMENDED SAVINGS* $443,129 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $395,425

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.6218: Turn off equipment when not in use $31,107 $30 $31,107
438,121
kWh
- -
02 2.7261: Install timers and/or thermostats $917 $30 $737
10,378
kWh
- $180
-
MMBtu
03 2.7261: Install timers and/or thermostats $158 $80 $158
2,227
kWh
- -
04 2.4221: Install compressor air intakes in coolest locations $1,646 $1,000 $1,534
21,608
kWh
$112
-
kW-mo/yr
-
05 2.2622: Replace existing chiller with high efficiency model $110,990 $170,000 $98,302
1,384,538
kWh
$12,688
-
kW-mo/yr
-
06 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $15,762 $46,000 $13,772
193,978
kWh
$1,989
-
kW-mo/yr
-
07 2.7232: Replace existing hvac unit with high efficiency model $36,995 $122,160 $34,502
485,940
kWh
$2,494
-
kW-mo/yr
-
08 2.7142: Utilize higher efficiency lamps and/or ballasts $1,628 $5,580 $1,628
22,932
kWh
- -
09 2.7232: Replace existing hvac unit with high efficiency model $8,905 $38,160 $8,167
115,024
kWh
$738
-
kW-mo/yr
-
10 2.7232: Replace existing hvac unit with high efficiency model $1,541 $6,960 $1,181
16,640
kWh
$360
-
kW-mo/yr
-
11 2.3513: Consider power loss as well as initial loads and load growth in down-sizing transformers $233,480 $1,905,000 $212,026
2,986,286
kWh
$21,454
-
kW-mo/yr
-
TOTAL RECOMMENDED $443,129 $2,295,000 $403,114
5,677,672
kWh
$39,835
-
kW-mo/yr
$180
-
MMBtu
TOTAL IMPLEMENTED $395,425 $2,133,600 $358,754
5,052,873
kWh
$36,491
-
kW-mo/yr
$180
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs