Assessment Year | 2017 |
---|---|
Principal Product | Processed Foods |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
150,000
ft2
|
Annual Production | 25,000,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,161,263 | 19,870,720 |
kWh
|
$0.058 |
Electricity Demand | $145,312 | 36,156 |
kW-mo/yr
|
$4.02 |
Electricity Fees | $101,645 | - |
|
- |
Natural Gas | $1,770,657 | 360,854 |
MMBtu
|
$4.91 |
TOTAL YEARLY COSTS | $3,178,877 | |||
RECOMMENDED SAVINGS* | $617,407 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $1,292 | $44 |
$344
5,933
kWh
|
$948
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,615 | $1,000 |
$6,924
119,381
kWh
|
$691
-
kW-mo/yr
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $724 | $300 |
$664
11,445
kWh
|
$60
-
kW-mo/yr
|
- | - | |
04 | 2.4221: Install compressor air intakes in coolest locations | $4,684 | $4,000 |
$4,134
71,268
kWh
|
$551
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,653 | $31,212 |
$24,337
419,608
kWh
|
$2,316
-
kW-mo/yr
|
- | - | |
06 | 2.4226: Use / purchase optimum sized compressor | $35,515 | $53,000 |
$32,287
556,665
kWh
|
$3,228
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $40,926 | $75,373 |
$37,368
644,280
kWh
|
$3,558
-
kW-mo/yr
|
- | - | |
08 | 2.1224: Replace boiler | $397,300 | $900,000 | - | - |
$147,300
-
MMBtu
|
$250,000 | |
09 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $9,040 | $22,500 |
$(-1,393.0)
(-24,024)
kWh
|
$(-132.6)
-
kW-mo/yr
|
$10,566
-
MMBtu
|
- | |
10 | 2.4226: Use / purchase optimum sized compressor | $18,899 | $58,000 |
$16,961
292,432
kWh
|
$1,938
-
kW-mo/yr
|
- | - | |
11 | 2.1233: Analyze flue gas for proper air/fuel ratio | $16,503 | $54,000 | - | - |
$16,503
-
MMBtu
|
- | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,262 | $8,160 |
$1,900
32,760
kWh
|
$362
-
kW-mo/yr
|
- | - | |
13 | 2.2443: Re-use or recycle hot or cold process exhaust air | $53,347 | $200,000 | - | - |
$53,347
-
MMBtu
|
- | |
14 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $337 | $1,488 |
$256
4,420
kWh
|
$80
-
kW-mo/yr
|
- | - | |
15 | 2.7232: Replace existing hvac unit with high efficiency model | $2,312 | $10,220 |
$2,111
36,400
kWh
|
$201
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $617,407 | $1,419,297 |
$125,892
2,170,568
kWh
|
$13,799
-
kW-mo/yr
|
$227,716
-
MMBtu
|
$250,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs