Assessment Year 2017
Principal Product Steel storage Cabinet
NAICS 337214: Office Furniture (except Wood) Manufacturing
SIC 2522: Office Furniture, Except Wood
Sales Range $10
M
to 50
M
# of Employees 37
Plant Area 160,000
ft2
Annual Production 2,000
ton
Production Hrs. Annual 4,420
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $80,084 1,182,750
kWh
Electricity Demand $20,389 5,009
kW-mo/yr
Electricity Fees $10,657 -
Natural Gas $70,370 14,289
MMBtu
TOTAL YEARLY COSTS $181,500
RECOMMENDED SAVINGS* $55,218 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,498 $1,000 $4,030
59,262
kWh
$468
-
kW-mo/yr
-
02 2.7313: Recycle air for heating, ventilation and air conditioning $18,942 $7,500 - - $18,942
-
MMBtu
03 2.2437: Recover waste heat from equipment $2,145 $1,500 - - $2,145
-
MMBtu
04 2.4221: Install compressor air intakes in coolest locations $892 $1,200 $725
10,659
kWh
$167
-
kW-mo/yr
-
05 2.7261: Install timers and/or thermostats $772 $1,100 $137
2,009
kWh
- $635
-
MMBtu
06 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $6,605 $12,500 $5,176
76,124
kWh
$1,429
-
kW-mo/yr
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $17,711 $33,950 $14,703
216,216
kWh
$3,008
-
kW-mo/yr
-
08 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,334 $5,100 $878
12,918
kWh
$456
-
kW-mo/yr
-
09 2.7142: Utilize higher efficiency lamps and/or ballasts $566 $2,525 $476
6,993
kWh
$90
-
kW-mo/yr
-
10 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,753 $8,500 $1,570
23,082
kWh
$183
-
kW-mo/yr
-
TOTAL RECOMMENDED $55,218 $74,875 $27,695
407,263
kWh
$5,801
-
kW-mo/yr
$21,722
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs