Assessment Year | 2015 |
---|---|
Principal Product | Rivet |
NAICS | 332722: Bolt, Nut, Screw, Rivet, and Washer Manufacturing |
SIC | 3452: Bolts, Nuts, Screws, Rivets, and Washers |
Sales Range | $1 M to 5M |
# of Employees | 4 |
Plant Area |
42,000
ft2
|
Annual Production | 133,000,000
pieces
|
Production Hrs. Annual | 2,000
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,802 | 463,900 |
kWh
|
$0.094 |
Electricity Demand | $6,468 | 1,382 |
kW-mo/yr
|
$4.68 |
Electricity Fees | $11,201 | - |
|
- |
Natural Gas | $21,814 | 2,270 |
MMBtu
|
$9.61 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,156 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,174 | $1,000 |
$1,893
20,142
kWh
|
$281
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,845 | $1,000 |
$1,710
18,189
kWh
|
$136
-
kW-mo/yr
|
- | - | - | |
03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $4,004 | $8,500 |
$(-72.9)
(-776)
kWh
|
$(-84.2)
-
kW-mo/yr
|
$4,161
-
MMBtu
|
- | - | |
04 | 2.4226: Use / purchase optimum sized compressor | $6,700 | $21,000 |
$6,396
68,041
kWh
|
$304
-
kW-mo/yr
|
- | - | - | |
05 | 2.7233: Use properly designed and sized hvac equipment | $1,557 | $4,800 | - | - |
$557
-
MMBtu
|
$1,000 | - | |
06 | 2.7233: Use properly designed and sized hvac equipment | $6,037 | $22,000 | - | - |
$2,037
-
MMBtu
|
- | $4,000 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,975 | $9,063 |
$1,586
16,875
kWh
|
$225
-
kW-mo/yr
|
- | $164 | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $887 | $4,200 |
$821
8,736
kWh
|
$66
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $25,180 | $71,563 |
$12,333
131,207
kWh
|
$927
-
kW-mo/yr
|
$6,756
-
MMBtu
|
$1,164 | $4,000 | ||
TOTAL IMPLEMENTED | $17,156 | $61,063 |
$8,803
93,652
kWh
|
$594
-
kW-mo/yr
|
$2,595
-
MMBtu
|
$1,164 | $4,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs