Assessment Year | 2014 |
---|---|
Principal Product | Roller and Spherical Bearings |
NAICS | 332991: Ball and Roller Bearing Manufacturing |
SIC | 3562: Ball and Roller Bearings |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
71,800
ft2
|
Annual Production | 200,000
pieces
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | New Jersey |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $342,935 | 2,507,009 |
kWh
|
$0.14 |
Natural Gas | $19,965 | 2,040 |
MMBtu
|
$9.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $110,079 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,907 | $48 |
$6,907
50,417
kWh
|
- | - | |
02 | 2.7261: Install timers and/or thermostats | $1,034 | $48 | - |
$1,034
-
MMBtu
|
- | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,422 | $393 |
$2,422
17,678
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,587 | $1,000 |
$4,587
33,482
kWh
|
- | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $589 | $166 |
$589
4,297
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $40,789 | $57,000 |
$39,456
288,000
kWh
|
- | $1,333 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,426 | $9,048 |
$6,309
46,051
kWh
|
- | $117 | |
08 | 2.4226: Use / purchase optimum sized compressor | $45,444 | $72,000 |
$45,444
331,704
kWh
|
- | - | |
09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,123 | $2,050 |
$1,622
11,840
kWh
|
$(-499.0)
-
MMBtu
|
- | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $291 | $877 |
$291
2,120
kWh
|
- | - | |
11 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $468 | $1,698 |
$468
3,416
kWh
|
- | - | |
TOTAL RECOMMENDED | $110,079 | $144,328 |
$108,094
789,005
kWh
|
$535
-
MMBtu
|
$1,450 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs