Assessment Year | 2014 |
---|---|
Principal Product | Siliconized Release Film |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $50 M to 100M |
# of Employees | 20 |
Plant Area |
208,000
ft2
|
Annual Production | 9,500
ton
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $501,757 | 8,775,132 |
kWh
|
$0.057 |
Electricity Demand | $55,078 | 15,428 |
kW-mo/yr
|
$3.57 |
Electricity Fees | $29,002 | - |
|
- |
Natural Gas | $190,329 | 41,250 |
MMBtu
|
$4.61 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $159,741 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,870 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,983 | - |
$3,547
62,230
kWh
|
$436
-
kW-mo/yr
|
- | |
02 | 2.2628: Utilize a less expensive cooling method | $35,793 | $130,000 |
$35,793
627,955
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,233 | $1,000 |
$2,837
49,767
kWh
|
$396
-
kW-mo/yr
|
- | |
04 | 2.7261: Install timers and/or thermostats | $3,209 | $1,225 |
$572
10,036
kWh
|
- |
$2,637
-
MMBtu
|
|
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $3,652 | $2,400 |
$2,495
43,770
kWh
|
$1,157
-
kW-mo/yr
|
- | |
06 | 2.2442: Preheat combustion air with waste heat | $9,750 | $6,900 | - | - |
$9,750
-
MMBtu
|
|
07 | 2.1224: Replace boiler | $93,869 | $72,460 | - | - |
$93,869
-
MMBtu
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,176 | $4,410 |
$3,705
65,000
kWh
|
$471
-
kW-mo/yr
|
- | |
09 | 2.7232: Replace existing hvac unit with high efficiency model | $681 | $1,400 |
$606
10,625
kWh
|
$75
-
kW-mo/yr
|
- | |
10 | 2.4221: Install compressor air intakes in coolest locations | $1,395 | $4,250 |
$1,070
18,779
kWh
|
$325
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $159,741 | $224,045 |
$50,625
888,162
kWh
|
$2,860
-
kW-mo/yr
|
$106,256
-
MMBtu
|
||
TOTAL IMPLEMENTED | $49,870 | $134,625 |
$45,244
793,758
kWh
|
$1,988
-
kW-mo/yr
|
$2,637
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs