Assessment Year | 2012 |
---|---|
Principal Product | Carbon Flat Roll Products |
NAICS | 331221: Rolled Steel Shape Manufacturing |
SIC | 3316: Cold-Rolled Steel Sheet, Strip, and Bars |
Sales Range | less than $500 k |
# of Employees | 62 |
Plant Area |
200,000
ft2
|
Annual Production | 60,000
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $73,794 | 1,054,200 |
kWh
|
$0.070 |
Electricity Demand | $21,653 | 10,137 |
kW-mo/yr
|
$2.14 |
Natural Gas | $56,586 | 4,556 |
MMBtu
|
$12.42 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $136,893 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,518 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $66,813 | - | - | - | $66,813 | - | - | |
02 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $16,976 | $7,660 | - | - | - |
$16,976
-
MMBtu
|
- | |
03 | 2.7243: Improve air circulation with destratification fans / other methods | $12,677 | $25,375 | - | - | - |
$12,677
-
MMBtu
|
- | |
04 | 2.7135: Install occupancy sensors | $9,659 | $24,370 |
$10,012
143,030
kWh
|
$13
-
kW-mo/yr
|
- | - | $(-366.0) | |
05 | 2.4226: Use / purchase optimum sized compressor | $8,856 | $28,000 |
$8,364
119,479
kWh
|
$492
-
kW-mo/yr
|
- | - | - | |
06 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,328 | $23,400 | - | - | - |
$7,328
-
MMBtu
|
- | |
07 | 4.625: Develop standard operating procedures | $6,689 | - |
$6,689
95,583
kWh
|
- | - | - | - | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,829 | $40 |
$3,616
51,660
kWh
|
$213
-
kW-mo/yr
|
- | - | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,360 | $6,400 |
$3,006
42,952
kWh
|
$354
-
kW-mo/yr
|
- | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $706 | $4,580 |
$710
10,152
kWh
|
$4
-
kW-mo/yr
|
- | - | $(-7.4) | |
TOTAL RECOMMENDED | $136,893 | $119,825 |
$32,397
462,856
kWh
|
$1,076
-
kW-mo/yr
|
$66,813 |
$36,981
-
MMBtu
|
$(-373.4) | ||
TOTAL IMPLEMENTED | $10,518 | $40 |
$10,305
147,243
kWh
|
$213
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs