Assessment Year 2009
Principal Product Novelty Ice Products
NAICS 311520: Ice Cream and Frozen Dessert Manufacturing
SIC 2024: Ice Cream and Frozen Desserts
Sales Range $100
M
to 500
M
# of Employees 245
Plant Area 101,000
ft2
Annual Production 7,465,499
units
Production Hrs. Annual 4,680
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $647,224 147,968,000
kWh
Electricity Demand $240,081 33,868
kW-mo/yr
Natural Gas $69,858 5,512
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $33,798 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $9,199

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
01 2.7447: Install vinyl strip / high speed / air curtain doors $9,385 $1,200 $1,390
33,519
kWh
- $7,995
-
MMBtu
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $6,837 $15,700 $4,804
111,720
kWh
$2,033
-
kW-mo/yr
- -
03 2.2437: Recover waste heat from equipment $3,929 $2,000 - - $3,929
-
MMBtu
-
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,543 $750 $2,657
57,989
kWh
$886
-
kW-mo/yr
- -
05 2.4231: Reduce the pressure of compressed air to the minimum required $2,148 $152 $1,558
36,234
kWh
$590
-
kW-mo/yr
- -
06 2.4235: Remove or close off unneeded compressed air lines $1,400 $500 $982
22,913
kWh
$418
-
kW-mo/yr
- -
07 2.4221: Install compressor air intakes in coolest locations $1,267 - $870
20,240
kWh
$397
-
kW-mo/yr
- -
08 2.1243: Use heat from boiler blowdown to preheat boiler feed water $1,204 $2,500 - - $1,204
-
MMBtu
-
09 2.2437: Recover waste heat from equipment $1,150 $2,500 - - $1,150
-
MMBtu
-
10 2.7135: Install occupancy sensors $1,045 - $1,045
23,774
kWh
- - -
11 2.2628: Utilize a less expensive cooling method $900 $1,500 - - $900
-
MMBtu
-
12 2.7142: Utilize higher efficiency lamps and/or ballasts $990 $2,500 $699
64,922
kWh
$266
-
kW-mo/yr
- $25
TOTAL RECOMMENDED $33,798 $29,302 $14,005
371,311
kWh
$4,590
-
kW-mo/yr
$15,178
-
MMBtu
$25
TOTAL IMPLEMENTED $9,199 $8,250 $5,271
166,925
kWh
$1,549
-
kW-mo/yr
$2,354
-
MMBtu
$25
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs