ITAC Assessment: LE0278
ITAC logo
ITAC Assessment: LE0278
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2008
Principal Product Elevator
NAICS 333921: Elevator and Moving Stairway Manufacturing
SIC 3534: Elevators and Moving Stairways
Sales Range $100
M
to 500
M
# of Employees 367
Plant Area 300,000
ft2
Annual Production 6,500
pieces
Production Hrs. Annual 6,000
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $564,671 10,147,970
kWh
Electricity Demand $138,266 19,357
kW-mo/yr
Natural Gas $623,797 103,391
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $264,658 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $103,151

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Ancillary Material Cost Savings
01 2.4321: Upgrade obsolete equipment $94,158 $132,748 $15,394
274,901
kWh
- - $78,764
-
MMBtu
-
02 2.6218: Turn off equipment when not in use $36,970 $760 $2,298
41,030
kWh
- - $34,672
-
MMBtu
-
03 2.7231: Use radiant heater for spot heating $17,728 $16,000 - - - $17,728
-
MMBtu
-
04 2.7261: Install timers and/or thermostats $12,408 $9,600 $12,408
221,562
kWh
- - - -
05 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle $10,716 $1,200 - - $(-1,344.0) $12,060
-
MMBtu
-
06 2.7496: Install partitions to reduce size of conditioned space $8,828 $7,000 - - - $8,828
-
MMBtu
-
07 2.2437: Recover waste heat from equipment $6,783 $7,000 - - - $6,783
-
MMBtu
-
08 2.2211: Use optimum temperature $7,669 $500 - - - $7,669
-
MMBtu
-
09 2.4231: Reduce the pressure of compressed air to the minimum required $5,894 $304 $4,694
83,826
kWh
$1,200
-
kW-mo/yr
- - -
10 2.4221: Install compressor air intakes in coolest locations $3,764 $800 $2,950
52,687
kWh
$814
-
kW-mo/yr
- - -
11 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $3,195 $1,824 $2,545
45,443
kWh
$650
-
kW-mo/yr
- - -
12 2.1131: Repair faulty insulation in furnaces, boilers, etc $2,387 $3,290 - - - $2,387
-
MMBtu
-
13 2.7261: Install timers and/or thermostats $1,785 $450 $1,785
31,882
kWh
- - - -
14 2.7142: Utilize higher efficiency lamps and/or ballasts $52,373 $142,010 $42,073
751,302
kWh
$10,731
-
kW-mo/yr
- - $(-431.0)
TOTAL RECOMMENDED $264,658 $323,486 $84,147
1,502,633
kWh
$13,395
-
kW-mo/yr
$(-1,344.0) $168,891
-
MMBtu
$(-431.0)
TOTAL IMPLEMENTED $103,151 $152,044 $48,701
869,657
kWh
$11,381
-
kW-mo/yr
- $43,500
-
MMBtu
$(-431.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs