Assessment Year | 2007 |
---|---|
Principal Product | Hardcover and Softcover Books |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2732: Book Printing |
Sales Range | $10 M to 50M |
# of Employees | 367 |
Plant Area |
190,000
ft2
|
Annual Production | 19,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $348,649 | 8,013,538 |
kWh
|
$0.044 |
Electricity Demand | $165,233 | 17,302 |
kW-mo/yr
|
$9.55 |
Natural Gas | $90,255 | 9,538 |
MMBtu
|
$9.46 |
Fuel Oil #2 | $102,634 | 9,193 |
MMBtu
|
$11.16 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $95,363 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,649 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4226: Use / purchase optimum sized compressor | $29,905 | $50,000 |
$20,066
456,005
kWh
|
$4,185
-
kW-mo/yr
|
- | $5,654 | |
02 | 2.7261: Install timers and/or thermostats | $29,184 | $20,000 |
$12,369
281,085
kWh
|
$5,577
-
kW-mo/yr
|
$11,238
-
MMBtu
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,625 | $20,000 |
$7,495
170,367
kWh
|
$3,130
-
kW-mo/yr
|
- | - | |
04 | 2.7135: Install occupancy sensors | $5,950 | $800 |
$5,950
135,233
kWh
|
- | - | - | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,181 | $300 |
$2,950
67,033
kWh
|
$1,231
-
kW-mo/yr
|
- | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,288 | $1,500 |
$1,612
36,688
kWh
|
$676
-
kW-mo/yr
|
- | - | |
07 | 2.6218: Turn off equipment when not in use | $1,147 | $750 |
$1,147
26,068
kWh
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,083 | $14,479 |
$8,523
193,752
kWh
|
$3,560
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $95,363 | $107,829 |
$60,112
1,366,231
kWh
|
$18,359
-
kW-mo/yr
|
$11,238
-
MMBtu
|
$5,654 | ||
TOTAL IMPLEMENTED | $25,649 | $17,829 |
$20,182
458,774
kWh
|
$5,467
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs