Assessment Year | 2006 |
---|---|
Principal Product | Fountain Syrup |
NAICS | 311930: Flavoring Syrup and Concentrate Manufacturing |
SIC | 2087: Flavoring Extracts and Flavoring Syrups, Not Elsewhere Classified |
Sales Range | n/a |
# of Employees | 75 |
Plant Area |
250,000
ft2
|
Annual Production | 60,000
Tgal
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $384,587 | 6,964,200 |
kWh
|
$0.055 |
Electricity Demand | $115,401 | 16,136 |
kW-mo/yr
|
$7.15 |
Natural Gas | $29,431 | 2,985 |
MMBtu
|
$9.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $121,803 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $94,577 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.5196: Use small number of high output units instead of many small inefficient units | $66,327 | $5,000 | - | - | - |
$41,818
-
Tgal
|
$24,509
-
Tgal
|
|
02 | 3.5132: Reuse rich white water in other applications | $14,590 | $20,000 | - | - | - |
$9,199
-
Tgal
|
$5,391
-
Tgal
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $9,683 | $6,700 |
$7,746
140,843
kWh
|
$1,937
-
kW-mo/yr
|
- | - | - | |
04 | 3.4151: Minimize water usage | $6,264 | $1,800 |
$590
10,729
kWh
|
- | - |
$3,577
-
Tgal
|
$2,097
-
Tgal
|
|
05 | 2.7226: Use computer programs to optimize hvac performance | $6,033 | $5,000 |
$4,827
87,759
kWh
|
$1,206
-
kW-mo/yr
|
- | - | - | |
06 | 2.6231: Utilize controls to operate equipment only when needed | $3,372 | $2,500 |
$3,372
61,304
kWh
|
- | - | - | - | |
07 | 2.8122: Use utility controlled power management | $3,000 | $100 | - | - | $3,000 | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,948 | $180,000 |
$8,758
159,245
kWh
|
$2,190
-
kW-mo/yr
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $1,586 | $450 |
$1,586
28,829
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $121,803 | $221,550 |
$26,879
488,709
kWh
|
$5,333
-
kW-mo/yr
|
$3,000 |
$54,594
-
Tgal
|
$31,997
-
Tgal
|
||
TOTAL IMPLEMENTED | $94,577 | $197,150 |
$22,917
416,676
kWh
|
$5,333
-
kW-mo/yr
|
- |
$41,818
-
Tgal
|
$24,509
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs