| Assessment Year | 2004 |
|---|---|
| Principal Product | Corrugated Board |
| NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $50 M to 100M |
| # of Employees | 89 |
| Plant Area |
160,000
ft2
|
| Annual Production | 80,857
ton
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $354,704 | 4,985,845 |
kWh
|
$0.071 |
| Electricity Demand | $91,171 | 11,417 |
kW-mo/yr
|
$7.99 |
| Natural Gas | $509,879 | 53,295 |
MMBtu
|
$9.57 |
| Fuel Oil #2 | $276,501 | 51,738 |
MMBtu
|
$5.34 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $698,568 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $49,557 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $575,674 | $984,000 |
$345,128
4,860,960
kWh
|
$78,622
-
kW-mo/yr
|
$151,924
-
MMBtu
|
- | |
| 02 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $29,156 | $14,088 | - | - |
$29,156
-
MMBtu
|
- | |
| 03 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $33,048 | $40,000 | - | - | - |
$33,048
-
MMBtu
|
|
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $19,946 | $48,000 | - | - |
$19,946
-
MMBtu
|
- | |
| 05 | 2.2136: Install / repair insulation on steam lines | $16,168 | $6,683 | - | - | - |
$16,168
-
MMBtu
|
|
| 06 | 2.4221: Install compressor air intakes in coolest locations | $8,604 | $40,000 |
$7,198
101,381
kWh
|
$1,406
-
kW-mo/yr
|
- | - | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $5,095 | - |
$4,351
61,286
kWh
|
$744
-
kW-mo/yr
|
- | - | |
| 08 | 2.6218: Turn off equipment when not in use | $5,089 | - |
$5,089
71,679
kWh
|
- | - | - | |
| 09 | 2.7447: Install vinyl strip / high speed / air curtain doors | $2,529 | $12,960 | - | - |
$2,529
-
MMBtu
|
- | |
| 10 | 2.4221: Install compressor air intakes in coolest locations | $2,299 | $1,200 |
$1,910
26,905
kWh
|
$389
-
kW-mo/yr
|
- | - | |
| 11 | 2.7441: Replace broken windows and/or window sash | $960 | $200 | - | - |
$960
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $698,568 | $1,147,131 |
$363,676
5,122,211
kWh
|
$81,161
-
kW-mo/yr
|
$204,515
-
MMBtu
|
$49,216
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $49,557 | $56,083 |
$11,350
159,870
kWh
|
$1,133
-
kW-mo/yr
|
$20,906
-
MMBtu
|
$16,168
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs